background image

BYPASS MODE OPERATION

The UPS will automatically transfer to Bypass Mode in the event it is overloaded, experiences an
internal failure and for the conditions listed below. When in bypass, the UPS will transfer the con-
nected load directly to the incoming utility power. 

When in bypass mode, Battery Mode will not be

available

. However, the utility power will continue to be passively filtered by the UPS. Additionally,

the UPS will sound an audible alarm and switch to Bypass Mode automatically upon the following 
conditions:

* The UPS has experienced an over temperature condition.
* The UPS has experienced an overload condition of 101 to 110% for over 120 seconds. 
* The UPS has experienced an overload condition of 111 to 150% for over 20 seconds.
* The UPS has experienced an overload condition of over 150%.
* The UPS detects a fault in the battery or UPS electronics.

The LCD display icon configuration on the left indicates the UPS is in 
Bypass Mode. The dark solid line shows the input connected directly to
the connected load. Another dark solid line shows the input power to 
the battery charger icon, then to the battery. The Fan is shown in low 
speed mode.

GREEN MODE OPERATION

When Green Mode is turned on using the UPS programming interface, the SSG unit will automatical-
ly switch to "Green Mode" (Bypass Mode), once the connected load drops to less than 3% of the
UPS’s rated output. The load will operate directly from utility power, similar to Bypass Mode.  The
LCD display will indicate the UPS is in Bypass Mode, the Green Mode bulb icon will be flashing. If
the load is increased to over 3% of the UPS output rating, the UPS will automatically switch back to
normal on-line operation.  All SSG models are shipped from the factory with Green Mode turned off.
To enable Green Mode, refer to the section on UPS Setup, Configuration & Programming. See the
green mode configuration section for further details and cautions.

How to Turn On the UPS (with utility power)

Once installation has been complete, the UPS can be powered up. With utility power present, turn
on the UPS input circuit breaker located on the front panel. The UPS will enter an Auto-Test state
and all of the LCD indicators will be illuminated flashing for ten seconds and then return to a 
normal state. The UPS will start up in bypass mode and after several seconds, should transfer to the
normal on-line mode. 

How to DC Start the UPS (without utility power)

In the event utility power is not available, the UPS may be started up in battery mode. To turn on the
UPS without utility power available, press and hold the "BYPASS" button. The UPS will start on 
battery and supply power to the connected loads until the batteries are depleted. Always recharge
the batteries immediately by connecting the UPS to utility power and turning on the UPS input circuit
breaker after any full battery discharge. For DC start operation the load segment control must be set
to Continuous Mode operation.

How to Turn Off the UPS  

To turn off the UPS:

While in normal on-line mode

, press the Bypass button for one second. The UPS will go into Bypass

Mode. Next, turn off the input circuit breaker. The unit will shut down after about 30 seconds.

While in battery mode: 

Press the Bypass button for one second. The unit will shut down after about

30 seconds.

19

Summary of Contents for SSG1.5KRM-1

Page 1: ...n SSG3KRM 1 3kVA 2100W 120Vac 20 C 55 C 4 F to 131 F Operation SSG3KRM HW 3kVA 2100W 120Vac 20 C 40 C 4 F to 104 F Operation SSG3KRM 2 3kVA 2100W 230Vac 20 C 55 C 4 F to 131 F Operation FALCON Electri...

Page 2: ...s LCD LED indicators icons 16 Function Test button 17 Set Alarm Silence button 17 How to display the UPS Parameters 17 Chapter 5 UPS Operation Operating Modes 18 Normal On line Mode 18 Battery Mode 18...

Page 3: ...nt Control Remote Emergency Power Off REPO Input Power Factor Correction Wide Input Voltage Window Precision Output Voltage Regulation Superior Brownout Surge and Transient Protection Optional Frequen...

Page 4: ...S in an indoor environment with an ambient temperature range specified by model number herein This UPS is designed for use with industrial scientific or data processing class equipment DO NOT USE TO P...

Page 5: ...Function Test and Set Alarm Silence buttons Two levels of audible alarms are also provided when the unit is operating on battery The SSG Series rear panel supports the following a Load Segment Contro...

Page 6: ...t design and produces a pure sinewave output with a 2 voltage regulation Having a very low output impedance it can supply the high current demands of high inrush and non linear loads Battery Packs The...

Page 7: ...d design in relation to the packaging s capacity and its intended use SAVE THE ORIGINAL SHIPPING CARTON INSERTS AND PACKING MATERIALS 6 Each consignment with packages bearing the lithium battery handl...

Page 8: ...Across The Batteries as Personnel Injury Fire or Explosion May Result 8 DANGER NEVER ATTEMPT TO CONNECT AN EXTENDED BATTERY BANK CONTAINING VRLA LEAD ACID BATTERIES TO A UPS CONTAINING INTERNAL LITHI...

Page 9: ...ing The SSG Series UPS may be shipped in a number of boxes depending on the model and configuration ordered The number of boxes you have received should be as indicated MODEL BATTERY MODULE NUMBER OF...

Page 10: ...er or into a 19 inch equipment rack Follow the appropriate instructions in either Rackmount UPS Setup or Free standing UPS Installation Rackmount UPS Setup All SSG Series models are shipped with front...

Page 11: ...istance needed 6 Attach the two mounting brackets to the rack s mounting rails The brackets allow adjustment of up to eight inches of the slide assembly mounting position front to back on the rack mou...

Page 12: ...e UPS into a dedicated wall receptacle that is protected by a circuit breaker or fuse in accordance with national and local electrical codes Use a 15 amp rated device for 1500 VA units 20 amp for the...

Page 13: ...ew the LCD board and rotate it 90 degrees to the correct position for viewing Use care when handling the LCD display and associated cabling Mount the front covers back and reinstall the screws SSG HW...

Page 14: ...5 8 217 5 243 13 184 6 8 261 7 150 283 5 15 221 7 8 304 5 SSG2 2KRM 1 HW SSG2 2KRM 2 HW SSGR 1 12 40 5 96Vdc 2 24 SSGR 1 SSGR 2 1 7 1 120Vac 3A 2 230Vac 1 5A 109Vdc 2 x 54Vdc 2A 2 Chargers 1A each 43...

Page 15: ...the unit and to prevent them from tipping over One additional set of mounting feet base extensions ships with each battery bank 3 Turn off the battery disconnect switch and connect the supplied batter...

Page 16: ...tery mode this icon will be displayed Battery Level The battery icon or LED indicates the battery capacity The more battery capacity available the more bars that will be illuminated Each bar represent...

Page 17: ...onds During that period the battery if first determined to be good will supply power to the UPS Should defective batteries be detected the audible alarm will sound one long tone and the UPS will conti...

Page 18: ...t to the charger and into the battery BATTERY MODE OPERATION The battery mode icon configuration is displayed during a loss of utility power or during excessively high line voltage conditions When in...

Page 19: ...flashing If the load is increased to over 3 of the UPS output rating the UPS will automatically switch back to normal on line operation All SSG models are shipped from the factory with Green Mode tur...

Page 20: ...status BIT 7 has a Dot or No Dot displayed for the function bit selected To select a dot or no dot for the function you are presently in press the Set Alarm Silence button to turn on Dot or turn off...

Page 21: ...st buttons at same time again and hold for one second The alarm buzzer will sound one short beep to acknowledge the UPS has stored the setting How to Set the UPS Output Voltage Function Bits 0 1 The S...

Page 22: ...ge the UPS has stored the settings 7 You must now restart the UPS before the new voltage setting will be in effect How to Set the UPS Load Segment Control Options Function Bits 3 4 5 6 Three condition...

Page 23: ...peatedly and move the dot to function BIT 4 for load segment 1 or BIT 6 for load segment 2 3 Press the Set Alarm Silence button once to turn on dot Status BIT 7 4 Press the Set Alarm Silence and Funct...

Page 24: ...into the Advanced Communications Option Slot the RS 232 port and UPSilon software may not be used The USB port may be used in conjunction with UPSilon software concurrently with the SNMP HTTP agent RS...

Page 25: ...PO connection is not used The REPO function provides an interface for a NFPA 70 NEC 645 11 compliant Remote Emergency Power Off REPO switch The switch must have a normally closed contact state that op...

Page 26: ...ote J1 J7 must be all configured 1 2 or 2 3 or UPS and PC may be damaged J9 Summery Alarm 1 2 Normally Closed Default 2 3 Normally Open J10 Low Battery 1 2 Normally Closed 2 3 Normally Open Default J1...

Page 27: ...SSG2 2KRM HW SSG3KRM HW Rear Panel Layout OUTPUT WIRING DETAILS 27 LS1 Neutral LS1 Line LS2 Neutral LS2 Line GND...

Page 28: ...place Batteries We suggest the battery pack s containing 10 12 year batteries have the batteries replaced every 8 10 years for SSG units that are operated and maintained in a 25 C environment Higher t...

Page 29: ...pack Take care not to destroy the packaging Compare new and old battery packs and verify that they are the same type If so proceed with the next step otherwise stop and contact Falcon Service 6 Line...

Page 30: ...on Service 7 Line up and slide in the new replacement battery packs with right polarity by verifying against the marked battery pack 8 Reinstall the battery stop plates with the screws previously remo...

Page 31: ...nnectors are provided on each battery module to allow for a daisy chain connection to all modules and the UPS Performing a Manual Battery Test Pressing the Function Test button for three seconds while...

Page 32: ...name and address of the nearest battery recycling facility NEVER open or mutilate the battery or batteries Released electrolyte is harmful to the skin and eyes It may be toxic A battery can present a...

Page 33: ...TING Audible Alarms The SSG Series UPS features audible alarm codes to alert the user of potential problems Please refer to the following table to identify and resolve alarms and the conditions causin...

Page 34: ...1 Bit 2 Bit 3 Bit 6 and Bit 7 errors the UPS must be immediately turned off and the Falcon service department contacted Attempting to turn the UPS back on may result in furter damage to its internal e...

Page 35: ...empting any troubleshooting always verify the UPS battery fuse is installed and the input voltage input plug and wiring are correct Please refer to the table below and attempt to solve the problem pri...

Page 36: ...nce to radio communications However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television recepti...

Page 37: ...use the original shipping container and packing materials will likely result in the unit being received by Falcon with shipping damage Falcon Electric will not assume any responsibility for shipping d...

Page 38: ...de of Falcon s control such as fire accidents impacts iv normal wear and tear such as cleaning and replacement of batteries The warranty is null and void if i the product is used in conjunction with l...

Page 39: ...es N A N A 6 minutes 18 minutes N A N A Recharge Time 8 Hours to 90 Transfer Time Line Fails Recovers Zero UPS to Bypass or Reverse 4ms After Overload Auto Transfer to UPS With Frequency Converter Opt...

Page 40: ...VRLA Batteries 12Vdc 7AH Number of Battery Packs 48Vdc 2 Recharge Time 8 Hours to 90 Transfer Time Line Fails Recovers Zero UPS to Bypass or Reverse 4ms After Overload Auto Transfer to UPS With Frequ...

Reviews: