Manual Bypass Function

A manual bypass button is located on the SSG front panel. When the UPS is operating from utility in
the normal on-line state, depressing this button will cause the UPS to transfer to bypass. Depressing
the bypass button again will return the UPS to the normal on-line condition.

Automatic Bypass Transfers

The SSG Series UPS will automatically switch to bypass to energize the connected load when the
UPS is first turned on, encounters an overload, encounters an over temperature condition, or upon a
UPS failure condition. Should any of these events occur, the UPS will transfer to bypass mode,
sound an audible alarm and provide a "bypass" indication on the LCD display.

Output Filter

As with the input filter stage, the output filter maintains conducted (EMC) and RFI levels below FCC
Class B limits.

3. 0 INSTALLATION

Unpacking

The SSG Series UPS may be shipped in a number of boxes, depending on the model and 
configuration ordered. The number of boxes you have received should be as indicated:

MODEL             

BATTERY MODULE                NUMBER OF  BOXES

SSG1.5KRM-X

n/a (internal battery pack)     

1 box shipped

SSG2.2KRM-X

1 battery module                    

2 boxes shipped

SSG3KRM-X 

1 battery module                   

2 boxes shipped   

If you have not received the proper number of boxes, please contact Falcon Electric Customer
Service at 1-800-842-6940.

This UPS is shipped complete with all cables required for operation, including UPSILON software,
and rackmount ears for 19" rackmount shelf mounting. A full list of the box contents is provided as
follows:

SSG1.5KRM-X  

SSG2.2KRM-X / SSG3KRM-X

Box 1 contains:                                          Box 1 contains:

UPS module with fitted battery pack            UPS module without battery 
RS-232 cable                                             RS-232 cable
Software CD                                              Software CD               
Manual                                                      Manual
19" rack ears (+ screws)                             19" rack ears (+ screws)                                    

Box 2 contains:            
Battery module
Battery connection cable
Keyhole hardware
19" rack ears (+ screws)
1 set of mounting plates & securing hardware

9

Summary of Contents for SSG1.5KRM-1

Page 1: ...n SSG3KRM 1 3kVA 2100W 120Vac 20 C 55 C 4 F to 131 F Operation SSG3KRM HW 3kVA 2100W 120Vac 20 C 40 C 4 F to 104 F Operation SSG3KRM 2 3kVA 2100W 230Vac 20 C 55 C 4 F to 131 F Operation FALCON Electri...

Page 2: ...s LCD LED indicators icons 16 Function Test button 17 Set Alarm Silence button 17 How to display the UPS Parameters 17 Chapter 5 UPS Operation Operating Modes 18 Normal On line Mode 18 Battery Mode 18...

Page 3: ...nt Control Remote Emergency Power Off REPO Input Power Factor Correction Wide Input Voltage Window Precision Output Voltage Regulation Superior Brownout Surge and Transient Protection Optional Frequen...

Page 4: ...S in an indoor environment with an ambient temperature range specified by model number herein This UPS is designed for use with industrial scientific or data processing class equipment DO NOT USE TO P...

Page 5: ...Function Test and Set Alarm Silence buttons Two levels of audible alarms are also provided when the unit is operating on battery The SSG Series rear panel supports the following a Load Segment Contro...

Page 6: ...t design and produces a pure sinewave output with a 2 voltage regulation Having a very low output impedance it can supply the high current demands of high inrush and non linear loads Battery Packs The...

Page 7: ...d design in relation to the packaging s capacity and its intended use SAVE THE ORIGINAL SHIPPING CARTON INSERTS AND PACKING MATERIALS 6 Each consignment with packages bearing the lithium battery handl...

Page 8: ...Across The Batteries as Personnel Injury Fire or Explosion May Result 8 DANGER NEVER ATTEMPT TO CONNECT AN EXTENDED BATTERY BANK CONTAINING VRLA LEAD ACID BATTERIES TO A UPS CONTAINING INTERNAL LITHI...

Page 9: ...ing The SSG Series UPS may be shipped in a number of boxes depending on the model and configuration ordered The number of boxes you have received should be as indicated MODEL BATTERY MODULE NUMBER OF...

Page 10: ...er or into a 19 inch equipment rack Follow the appropriate instructions in either Rackmount UPS Setup or Free standing UPS Installation Rackmount UPS Setup All SSG Series models are shipped with front...

Page 11: ...istance needed 6 Attach the two mounting brackets to the rack s mounting rails The brackets allow adjustment of up to eight inches of the slide assembly mounting position front to back on the rack mou...

Page 12: ...e UPS into a dedicated wall receptacle that is protected by a circuit breaker or fuse in accordance with national and local electrical codes Use a 15 amp rated device for 1500 VA units 20 amp for the...

Page 13: ...ew the LCD board and rotate it 90 degrees to the correct position for viewing Use care when handling the LCD display and associated cabling Mount the front covers back and reinstall the screws SSG HW...

Page 14: ...5 8 217 5 243 13 184 6 8 261 7 150 283 5 15 221 7 8 304 5 SSG2 2KRM 1 HW SSG2 2KRM 2 HW SSGR 1 12 40 5 96Vdc 2 24 SSGR 1 SSGR 2 1 7 1 120Vac 3A 2 230Vac 1 5A 109Vdc 2 x 54Vdc 2A 2 Chargers 1A each 43...

Page 15: ...the unit and to prevent them from tipping over One additional set of mounting feet base extensions ships with each battery bank 3 Turn off the battery disconnect switch and connect the supplied batter...

Page 16: ...tery mode this icon will be displayed Battery Level The battery icon or LED indicates the battery capacity The more battery capacity available the more bars that will be illuminated Each bar represent...

Page 17: ...onds During that period the battery if first determined to be good will supply power to the UPS Should defective batteries be detected the audible alarm will sound one long tone and the UPS will conti...

Page 18: ...t to the charger and into the battery BATTERY MODE OPERATION The battery mode icon configuration is displayed during a loss of utility power or during excessively high line voltage conditions When in...

Page 19: ...flashing If the load is increased to over 3 of the UPS output rating the UPS will automatically switch back to normal on line operation All SSG models are shipped from the factory with Green Mode tur...

Page 20: ...status BIT 7 has a Dot or No Dot displayed for the function bit selected To select a dot or no dot for the function you are presently in press the Set Alarm Silence button to turn on Dot or turn off...

Page 21: ...st buttons at same time again and hold for one second The alarm buzzer will sound one short beep to acknowledge the UPS has stored the setting How to Set the UPS Output Voltage Function Bits 0 1 The S...

Page 22: ...ge the UPS has stored the settings 7 You must now restart the UPS before the new voltage setting will be in effect How to Set the UPS Load Segment Control Options Function Bits 3 4 5 6 Three condition...

Page 23: ...peatedly and move the dot to function BIT 4 for load segment 1 or BIT 6 for load segment 2 3 Press the Set Alarm Silence button once to turn on dot Status BIT 7 4 Press the Set Alarm Silence and Funct...

Page 24: ...into the Advanced Communications Option Slot the RS 232 port and UPSilon software may not be used The USB port may be used in conjunction with UPSilon software concurrently with the SNMP HTTP agent RS...

Page 25: ...PO connection is not used The REPO function provides an interface for a NFPA 70 NEC 645 11 compliant Remote Emergency Power Off REPO switch The switch must have a normally closed contact state that op...

Page 26: ...ote J1 J7 must be all configured 1 2 or 2 3 or UPS and PC may be damaged J9 Summery Alarm 1 2 Normally Closed Default 2 3 Normally Open J10 Low Battery 1 2 Normally Closed 2 3 Normally Open Default J1...

Page 27: ...SSG2 2KRM HW SSG3KRM HW Rear Panel Layout OUTPUT WIRING DETAILS 27 LS1 Neutral LS1 Line LS2 Neutral LS2 Line GND...

Page 28: ...place Batteries We suggest the battery pack s containing 10 12 year batteries have the batteries replaced every 8 10 years for SSG units that are operated and maintained in a 25 C environment Higher t...

Page 29: ...pack Take care not to destroy the packaging Compare new and old battery packs and verify that they are the same type If so proceed with the next step otherwise stop and contact Falcon Service 6 Line...

Page 30: ...on Service 7 Line up and slide in the new replacement battery packs with right polarity by verifying against the marked battery pack 8 Reinstall the battery stop plates with the screws previously remo...

Page 31: ...nnectors are provided on each battery module to allow for a daisy chain connection to all modules and the UPS Performing a Manual Battery Test Pressing the Function Test button for three seconds while...

Page 32: ...name and address of the nearest battery recycling facility NEVER open or mutilate the battery or batteries Released electrolyte is harmful to the skin and eyes It may be toxic A battery can present a...

Page 33: ...TING Audible Alarms The SSG Series UPS features audible alarm codes to alert the user of potential problems Please refer to the following table to identify and resolve alarms and the conditions causin...

Page 34: ...1 Bit 2 Bit 3 Bit 6 and Bit 7 errors the UPS must be immediately turned off and the Falcon service department contacted Attempting to turn the UPS back on may result in furter damage to its internal e...

Page 35: ...empting any troubleshooting always verify the UPS battery fuse is installed and the input voltage input plug and wiring are correct Please refer to the table below and attempt to solve the problem pri...

Page 36: ...nce to radio communications However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television recepti...

Page 37: ...use the original shipping container and packing materials will likely result in the unit being received by Falcon with shipping damage Falcon Electric will not assume any responsibility for shipping d...

Page 38: ...de of Falcon s control such as fire accidents impacts iv normal wear and tear such as cleaning and replacement of batteries The warranty is null and void if i the product is used in conjunction with l...

Page 39: ...es N A N A 6 minutes 18 minutes N A N A Recharge Time 8 Hours to 90 Transfer Time Line Fails Recovers Zero UPS to Bypass or Reverse 4ms After Overload Auto Transfer to UPS With Frequency Converter Opt...

Page 40: ...VRLA Batteries 12Vdc 7AH Number of Battery Packs 48Vdc 2 Recharge Time 8 Hours to 90 Transfer Time Line Fails Recovers Zero UPS to Bypass or Reverse 4ms After Overload Auto Transfer to UPS With Frequ...

Reviews: