Battery Information
Never discard the UPS, battery pack, or individual batteries in the trash. Contact your local recycling or
hazardous waste center for information on proper disposal of the used batteries. The depleted batteries
or packs may be returned to the Falcon Service Center at the end user’s expense for recycling. Prior to
returning the depleted batteries or packs, please contact the Falcon Service Center and obtain a Return
Material Authorization (RMA) number.
Never dispose of used batteries or the UPS in the trash or a land
fi
ll as it is a violation of federal and
state laws. The UPS and batteries must be recycled. For UPS and battery recycling information, please
contact your local recycling or hazardous waste center.
Battery Storage
If the UPS system is to be stored for an extended period, the following precautions should be observed
to maximize battery life:
Connect UPS to a properly rated outlet for at least 24 hours to ensure batteries are in a fully
charged state prior to long-term storage.
The ideal ambient temperature for storage should be between -15°C to 40°C. (5°F to 104°F)
When operated in temperatures above 25°C, the battery service life will be reduced.
Remove the battery fuse or turn off the battery circuit breaker prior to storage.
Battery specifications subject to change without notice. Visit battery manufacturers website for
latest information
Battery Capacity Retention
The table below provides the maximum allowable storage period based on ambient temperature. The
recommendations below yield about 60% battery capacity at maximum storage period. The batteries
require recharge after storage.
Temperature
Maximum Storage
Period (Months)
Recommendation
5°C / 41°F
19
Good condition. Charge
prior to use. (Minimum 8
hours to 90% capacity
using UPS charger.)
25°C / 77°F
10
30°C / 86°F
6
40°C / 104°F
3.5