CHAPTER 3
CHAPTER 3
Preliminary Operating Instruction
GND1
1
GND2
GND3
GND4
2
3
4
C
ON
OFF
GND5
5
Not
Used
TEMPERATURE
SENSOR
SENSAPHONE REAR PANEL
UPS & INTERFACE CABLE CONNECTIONS
GND1 Temperature Sensor Return
1. ---- Temperature Sensor Signal
GND2 Utility Loss Return (orange wire)
2. ---- Utility Loss Signal (brown wire)
GND3 On Battery Return (blue wire)
3 ---- On Battery Signal (white wire)
GND4 Alarm/On bypass Return (green wire)
4 ---- Alarm/On bypass Signal (yellow wire)
GND5 UPS Output Control Return (gray wire)
5 ---- UPS Output Control Signal (violet wire)
"Alert Condition 2" (Utility Loss to UPS)
"Temperature Alert Condition 1"
"Alert Condition 3" (UPS on at low battery)
"Alert Condition 4" (UPS in alarm or bypass)
Turns UPS outlets 1 & 2 on & off
Note: UPS outlets 1& 2 are controllable by the Sensaphone and backed up by the UPS.
UPS outlet 3 is on continuously and backed up by the UPS.
UPS outlet 4 is on continuously and backed up by the UPS. CONNECT SENSAPHONE
INPUT POWER PLUG TO THIS OUTLET
"Loss of Sensaphone Input Power Alert Condition" (UPS lost it's output)
SENSAPHONE CABLE CONNECTIONS & ASSOCIATED ALERT CONDITIONS
UPS & SENSAPHONE ALERTS
ALERT 1
Room temperature (sensor located on the Sensaphone rear panel)
ALERT 2
Loss of utility voltage sensed at the UPS input. UPS in battery mode.
ALERT 3
UPS at low battery, approximately one minute of backup remaining.
ALERT 4
UPS is in bypass as a normal part of the UPS startup. Ignore and
reset the alarm.
OR
UPS has been manually placed in bypass using the front panel button.
OR
UPS is in an alarm condition. Refer to the SG user’s manual for alarm
details.
SENSAPHONE POWER ALERT The Sensaphone has lost input power. The UPS
has lost its output due to:
a. A sustained power outage and UPS shutdown
b. The UPS was manually turned off.
c. The UPS failed and lost output