24
After AC failed and USHA had broadcast shutdown request to clients, The UPS will not be turn off
if AC restored and this option had selected. If this option isn't selected, the UPS will be turn off by
USHA even AC restored.
Different Events
A/C Fail
Shutdown will occur when the AC input fails.
Battery Low
Shutdown will occur for the battery low condition.
UPS Overload
Shutdown occurs if the output of the UPS is overload. Please check the configuration in UPS
Shutdown menu for UPS Overload.
UPS Over Temperature
Shutdown occurs if the internal temperature of the UPS is over the pre-set value. Please check the
configuration in UPS Shutdown menu for UPS Over Temperature.
Weekly Schedule
This Shutdown occurs as per the timings given in the Weekly Schedule shutdown table.
Special Day
This Shutdown occurs as per the Day & Time mentioned in the Special Day shutdown table.
EMD Temperature over Threshold
Shutdown occurs when EMD temperature sensor detects over high temperature.
EMD Alarm-1
Shutdown occurs when alarm-1 sensor detects an active alarm.
EMD Alarm-2
Shutdown occurs when alarm-2 sensor detects an active alarm.
Weekly Schedule
This page lets you modify the parameters of the shutdown / restart events associated with the
days of the week. Please make sure the Weekly Schedule option is enable in the UPS Shutdown
menu.