background image

 

 

15

 

 CAUTION                                 

                                      
When the UPS is in Normal On-line mode, pressing the BYPASS button once will put the UPS 
into BYPASS MODE. During this time, should the utility power become unavailable, the UPS 
will shut down.  
 
Once the unit is in BYPASS MODE operation, pressing this button again will force UPS back to 
On-line operation.  
 

5.0 OPERATION

 

 

OPERATING MODES 

The display shows the UPS status through the graph LCD for each mode

.  

 

NORMAL ON-LINE MODE  

During normal on-line operation, utility power provides energy to the UPS. The filters, power 
factor corrector and the inverter process the power to provide computer grade power to 
connected loads. The UPS maintains the batteries in a fully charged state. 

 

 

 
 
All indicators are stable except Alarm Buzzer. The LCD displays 
the % of load, Inverter, PFC, Line, Charger and Battery. The Fan is 
at medium speed.   
The Solid line shows the power flow from input to load and 
battery. The load is being powered from the UPS inverter.

 

 
 
 
 

BATTERY MODE 

Battery mode is displayed during high input voltage conditions or a utility power failure. When 
in battery mode, the UPS battery supplies energy through the DC to DC converter to the 
Inverter to power the connected load. During the battery discharging, the audible alarm beeps. 
The rate of the beeping will increase as the battery runs low (low battery), prior to UPS shut 
down.  Once this warning is sounded, you have less than a minute of battery runtime left. 
When utility power has been restored, after UPS has shutdown, the UPS will automatically 
restart. For approximate battery run times, refer to the Battery Run Time charts in this manual. 
The run-time is based on a resistive load and an ambient temperature of 77

o

F (25

o

C) 

 
The Display shows the UPS in BATTERY MODE. The solid line is 
from battery to inverter with boost illuminated. The Fan high 
speed mode is illuminated. The bars, in the battery display 
indicate the amount of battery capacity remaining; each bar 
represents a 25% capacity level. As capacity decreases, fewer 
bars remain illuminated. When the input voltage returns, the 
charger indicator will illuminate.

 

 

Summary of Contents for XG1.5K-1T

Page 1: ...All rights reserved All other brand names and trademarks are the property of their respective owners The information stated in this document is subject to change without notice 2005 10 14 Falcon Falco...

Page 2: ...LAY AND CONTROLS 12 Indicators and LCD Display Controls 5 0 OPERATION 15 Operating Modes Turning UPS On Turning UPS Off 6 0 CONFIGURATION 17 Green Mode Setting Voltage Setting 7 0 COMMUNICATION 19 RS...

Page 3: ...be retained in the event the UPS needs to be returned for service INSTALLATION Install this UPS in a clean environment free from moisture flammable gases or fumes and corrective substances Operate th...

Page 4: ...res of XG series UPS as well as detailing operation configuration and troubleshooting The specifications section states all of the detailed parameters of operation for the Series and provides general...

Page 5: ...ad while operation from a utility source with abnormally low input voltage DC DC CONVERTER The DC DC converter utilizes energy from battery and boosts up the DC bus voltage to a level required by the...

Page 6: ...over temperature over input current over crest factor load designed for 3 1 nonlinear load or a UPS failure condition Should any of these events occur the UPS will automatically transfer to bypass mod...

Page 7: ...ge claim within 15 days to Falcon Electric Inc CAUTION The UPS and Battery Module are heavy Take proper precautions when lifting or moving them Install the UPS indoors in a controlled environment plac...

Page 8: ...and secure with the supplied screws 3 If installing the Battery Module repeat above STEPS 4 For slide rail installations fasten the inner parts of the slide rails to the UPS on both sides with the scr...

Page 9: ...load may be connected Ensure the load equipment is turned off plug all loads into the output receptacles on the rear of the UPS Plug the UPS into a dedicated wall receptacle properly protected by a ci...

Page 10: ...g To orient the LCD display for vertical Mini Tower viewing remove the front plastic bezel by unscrewing the screws The unit has two front panel covers Remove the left cover first Next pull the right...

Page 11: ...e battery modules have been designed to be placed on one side of the UPS or stacked beneath the UPS 1 Visually inspect the battery module for any freight damage Report damage to the carrier and Falcon...

Page 12: ...f the extended battery module 6 If an extended battery module has been connected refer to the Battery Run Time charts in this manual for the approximate runtime available 4 0 DISPLAY CONTROLS The diag...

Page 13: ...he more bars that will be illuminated Each bar represents 25 of the UPS output rating Inverter When Inverter is functioning this symbol will be illuminated PFC When PFC is functioning this symbol will...

Page 14: ...e to operate from the utility voltage without going to battery mode During the battery test the output of the UPS will not be affected SET ALARM SILENCE BUTTON This button has three functions Disable...

Page 15: ...nverter BATTERY MODE Battery mode is displayed during high input voltage conditions or a utility power failure When in battery mode the UPS battery supplies energy through the DC to DC converter to th...

Page 16: ...urned on the XG unit is automatically switched to GREEN MODE once the connected load drops to less than 3 of the UPS rated output The load will operate directly from utility power similar to BYPASS MO...

Page 17: ...up CONFIGURATION Mode To put the UPS into configuration mode press the FUNTION TEST and SET ALARM SILENCE buttons at same time and hold them for one second The unit will emit one audible beep and then...

Page 18: ...ss the SET ALARM SLIENCE and FUNCTION TEST buttons at same time again and hold for one second The alarm buzzer will sound one short beep to acknowledge the UPS has stored the setting To Disable Factor...

Page 19: ...nd move the dot to function BIT 1 5 Press the SET ALARM SLIENCE button once or twice to Enable dot Status BIT 7 6 Press the SET ALARM SLIENCE and FUNCTION TEST buttons at same time again and hold for...

Page 20: ...ected and the supplied UPSILON Computer Shutdown and Management software has been properly installed on the connected computer a high level of protection against lost or corrupted files is in effect P...

Page 21: ...UPS is on battery will turn the UPS off 8 Alarm Upon a UPS fault or failure the contact activates J3 1 2 short N O J3 2 3 short N C 9 JP3 shorted Alarm common all other shorted JP commons JP3 open Ala...

Page 22: ...t is recommended to plug the UPS in for at least 24 hours every four to six months to ensure full recharge of the batteries WHEN TO REPLACE BATTERIES We suggest that you replace the battery pack every...

Page 23: ...k 5 Unpack the new battery pack Take care not to destroy the packing Compare new and old battery pack to make sure they are the same If so proceed with next the STEP otherwise STOP and contact Falcon...

Page 24: ...eplacement battery packs with right polarity by verifying against the marked battery pack 8 Reinstall the battery stoppers with the screws 9 Reinstall panels to the unit with the screws 10 Connect the...

Page 25: ...or metal parts on top of batteries Do not attempt to alter any battery wiring or connectors Attempting to alter wiring can cause injury Do not dispose of batteries in a fire The batteries may explode...

Page 26: ...tion in action Verify the input AC voltage is not too low remove some load from UPS output Seven short beeps followed by three long beeps every five seconds Battery low after utility loss Save the dat...

Page 27: ...run an UPS UPS drops the load and is in bypass mode with alarm Check the load status the UPS may be overloaded UPS battery time is not long enough or the unit does not run on battery at all Test the...

Page 28: ...oad Protection Fuse Power Cord 6 ft attached with NEMA 5 15 plug OUTPUT Output Receptacles 4 NEMA 5 15R Voltage 100 110 115 120 user selectable VAC Voltage Regulation 2 of nominal Frequency 60 Hz Wave...

Page 29: ...L5 20 plug 6 ft attached with NEMA L5 30 plug OUTPUT Output Receptacles 4 NEMA 5 15R 1 L5 30R 1 5 15 4 NEMA 5 15R or 1 L5 30R 1 5 15R Voltage 100 110 115 120 user configurable VAC Voltage Regulation 2...

Page 30: ...Option for SNMP USB card or DB 9 card SOFTWARE UPSILON Supplied bundled to support Windows 95 98 NT ME 2000 XP BATTERY RUN TIMES RUN TIME CHART in Minutes UPS Model 800VA 560W 1000VA 700W 1500VA 1050W...

Page 31: ...and Falcon Electric Inc will not knowingly sell this product for use with life support and other designated critical devices ANY SUCH USE BY A USER AUTOMATICALLY VOIDS AND DISCLAIMS ANY AND ALL WARRA...

Page 32: ...r agrees to pay for all shipping costs associated with transportation of the loaner unit both from and return to the Falcon Electric U S Service Center c All shipping costs for product submitted beyon...

Reviews: