Chapter 6 Function Introduction
Shenzhen Hpmont Technology Co., Ltd.
- 26 -
HD3N-L Series User Manual V1.0
6.1.4
D03: Running Status Parameters
Ref. Code
Function Description
Setting Range [Default]
D03.01
Input terminal status
[Actual value]
Display input terminal status.
Standard LCD display is hexadecimal number, optional LCD display is 16-bit binary number.
Each bit (binary) represents a different input terminal, see the table below.
•
0: DI terminals disconnects with common terminals.
•
1: DI terminals connects with common terminals.
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
DI8
DI7
DI16
DI5
DI4
DI3
DI2
DI1
123
D03.02
Output terminal status
[Actual value]
Display output terminal status.
Standard LCD display is hexadecimal number, optional LCD display is 16-bit binary number.
Each bit (binary) represents a different output terminal, see the table below.
•
Positive logic: 0 means invalid, 1 means valid.
•
Negative logic: 0 means valid, 1 means invalid.
Bit3
Bit2
Bit1
Bit0
RLY2
RLY1
DO2
DO1
123
D03.03
Modbus status
[Actual value]
Display Modbus communication status.
0: Normal.
1: Communication timeout.
2: Incorrect data frame head.
3: Incorrect data frame checking.
4: Incorrect data frame content.
D03.04
Total time at power-on (h)
[Actual value]
D03.05
Total running time (h)
[Actual value]
D03.06
Running times
[Actual value]
D03.07
Present fault
[Actual value]