Chapter 6 Function Introduction
HD3N-L Series User Manual V1.0
- 31
-
6.2.5
F04: Analogue Curve Parameters
Ref. Code
Function Description
Setting Range [Default]
F04.00
Setting curve
0,1 [0]
0: Line 1.
1: Line 2.
F04.01
Line 1 Min. setting
0.0 - F04.03 [0.0%]
F04.02
Corresponding value of line 1 Min. setting
0.0 - 100.0 [0.0%]
F04.03
Line 1 Max. setting
F04.01 - 100.0 [100.0%]
F04.04
Corresponding value of line 1 Max. setting
0.0 - 100.0 [100.0%]
F04.05
Line 2 Min. setting
0.0 - F04.07 [0.0%]
F04.06
Corresponding value of line 2 Min. setting
0.0 - 100.0 [0.0%]
F04.07
Line 2 Max. setting
F04.05 - 100.0 [100.0%]
F04.08
Corresponding value of line 2 Max. setting
0.0 - 100.0 [100.0%]
F04.01 - F04.04 define line 1. F04.05 - F04.08 define line 2.
Both can independently realize the positive and negative characteristics, as shown in the figure below.
6.2.6
F05: Speed Parameters
Ref. Code
Function Description
Setting Range [Default]
F05.00
Multi-speed 0
0.000 - F00.02 [0.000m/s]
F05.01
Multi-speed 1
0.000 - F00.02 [0.000m/s]
F05.02
Multi-speed 2
0.000 - F00.02 [0.000m/s]
F05.03
Multi-speed 3
0.000 - F00.02 [0.000m/s]
F05.04
Multi-speed 4
0.000 - F00.02 [0.000m/s]
F05.05
Multi-speed 5
0.000 - F00.02 [0.000m/s]
F05.06
Multi-speed 6
0.000 - F00.02 [0.000m/s]
F05.07
Multi-speed 7
0.000 - F00.02 [0.000m/s]
F05.00 - F05.07 define the MS running speed which is used in MS run mode.
F00.02 is the rated speed of elevator.
F05.08
Inspection run speed
0.000 - 0.630 [0.200m/s]
Defines the running speed of elevator in the inspection run mode.
F05.09
Emergency run speed
0.000 - F00.02 [0.100m/s]
Defines the running speed of elevator in the emergency run mode.
F04.01
F04.05
F04.03
F04.07
F04.04
F04.08
F04.02
F04.06
AI reference
Setting
corresponding value
F04.01
F04.05
F04.03
F04.07
F04.02
F04.06
F04.04
F04.08
AI reference
Setting
corresponding value