Shenzhen Hpmont Technology Co., Ltd.
Appendix A Parameters
HD3N-L Series User Manual V1.0
- 63
-
Appendix A
Parameters
Attributes are changed:
X: It denotes that the setting of this parameter cannot be modified when the controller is in run status.
O: It denotes that the setting of this parameter can be modified when the controller is in run status.
*: It denotes that the value of this parameter is the actual value which cannot be modified.
Ref. Code
Function
Setting Range
Default
Unit
Attribute Setting
D00: Status Display Parameter (on pages 24 - 25)
D00.00
Controller series
3N-L
Actual
*
D00.01
DSP software version
0.00 - 9.99
Actual
*
D00.02
DSP non-standard software
version
0.00 - 9.99
Actual
*
D00.03
Keypad Software version
0.00 - 9.99
Actual
*
D00.04
Elevator running status
The standard LCD display is
hexadecimal number, and the
optional LCD display is a 16-bit
binary number
Bit0: Controller enable
Bit1: Inspection run
Bit2: Multi-speed run
Bit3: Analogue run
Bit8: Brake feedback input
Bit9: Contactor feedback input
Bit12: Multi-speed terminal 1
Bit13: Multi-speed terminal 2
Bit14: Multi-speed terminal 3
Bit15: Emergency run
Actual
*
D00.05
Controller rated current
0.1 - 999.9A
Actual
D00.07
Controller status
The standard LCD display is
hexadecimal number, and the
optional LCD display is a 16-bit
binary number
Bit0: Controller fault
Bit1: Run/stop
Bit2: UP
Bit3: DN
Bit5&Bit4: Acc./Dec./constant
Bit6: Zero-speed signal
Bit7: Zero-speed running
Bit8: Auto-tuning
Bit9: Speed reached
Bit10: Ready to run
Bit11: Brake output
Bit12: Contactor output
Actual
*
A