Chapter 7 Elevator Application Guidance
Shenzhen Hpmont Technology Co., Ltd.
- 52 -
HD3N-L Series User Manual V1.0
Ref. Code
Function
Value
Remark
F07.02
Motor rated current
Depend on actual value
F07.03
Motor rated frequency
Depend on actual value
F07.04
Motor rated RPM
Depend on actual value
F08.00/F08.02
Low/high speed ASR KP
500
Adjust according to running
effect.
Generally use the default value
F08.01/F08.03
Low/high speed ASR KI
500
F08.04
ASR PI swithcing frequency 1
10.00Hz
F08.05
ASR PI swithcing frequency 2
15.00Hz
Table 7-2 Terminal MS run parameter
Ref. Code
Function
Value
Remark
F00.05
Operating mode
2
Terminal MS control
F02.02
Start zero-speed hold time
0.5s
Adjust according to the
situation of run contactor and
brake at motor start and stop
F02.06
Stop zero-speed hold time
0.5s
F03.00
Acc. speed
0.700m/s
2
Set according to the elevator
speed and running effect
F03.01
Start Acc. jerk
0.350m/s
3
F03.02
End Acc. jerk
0.600m/s
3
F03.03
Dec. speed
0.700m/s
2
F03.04
Start Dec. jerk
0.600m/s
3
F03.05
End Dec. jerk
0.350m/s
3
F03.06
Inspection Acc. speed
0.200m/s
2
F03.07
Inspection Dec. speed
1.000m/s
2
F03.13
Stop Dec. jerk
0.350 m/s
3
F05.00
Multi-speed 0
0
As actual value
F05.01
Multi-speed 1
Releveling speed
F05.02
Multi-speed 2
Creep speed
F05.03
Multi-speed 3
Emergency stop
F05.04
Multi-speed 4
Inspection speed
F05.05
Multi-speed 5
Normal low speed
F05.06
Multi-speed 6
Normal speed
F05.07
Multi-speed 7
Normal high speed
F12.01
DI1 function
1
Controller enabled (EN)
F12.02
DI2 function
2
UP
F12.03
DI3 function
3
DN
F12.04
DI4 function
4
Multi-speed 1 (MS1)
F12.05
DI5 function
5
Multi-speed 2 (MS2)
F12.06
DI6 function
6
Multi-speed 3 (MS3)
F12.15
DO1 function
2
Running
F12.16
DO2 function
3
Zero-speed running
F12.17
RLY1 function
14
Controller fault
F16.07
Multi-speed inspection
4
Multi-speed inspection run