6.2.19
F20: Function-boost Parameters 2
Ref. Code
Function Description
Setting Range [Default]
F20.00 Start DC brake current
50 - 150 [100%]
F20.01 Duration of start DC brake current
0.0 - 3.0 [0.0s]
When F00.01 ≠ 2 (VC control), F20.00 and F20.01 are valid.
When F20.01 = 0, start DC braking function is invalid.
F20.02 DI enable function
0,1 [0]
0: Original plan.
•
The run contactor can be output only when there is an enable signal.
1: New plan.
•
When there is a running command signal, open the run contactor. when the run contactor signal is
turned on, if the enable signal is detected, it can continue to run.
•
It is used when the controller controls the run contactor, and uses the run contactor feedback contact as
an enable signal.
F20.03 Output contactor open time
0 - 9 [0s]
0: Keep open.
1 - 9: After the directional signal contactor opens for F20.03, the output contactor is closed after the enable
signal is still invalid.
F20.04 Ground detection before running
0,1 [0]
0: Detection.
1: No detection.
F20.05 Brake open frequency
0.00 - 10.00 [0.00Hz]
F20.06 Brake open current
0 - 150 [0%]
F20.07 Restore customized parameters
0 - 9 [0]
F20.13 Emergency run torque limit
70.0 - 200.0 [0.0%]
F20.14 Emergency run undervoltage point setting
160 - 220 [190V]
F20.15 Emergency run parameter
000 - 110 [110]
Unit: Unused
Ten: Emergency run torque limited (F20.19)
•
0: F20.19 no functional.
•
1: F20.19 functional.
Hundred: Emergency run mode determine
•
0: F00.01.
•
1: V/f control.
F20.17 Search speed of light load current method when emergecy run
0.020 - 0.200 [0.150m/s]
F20.18 Search time of light-load current method when emergency run
0.300 - 3.000 [0.500s]
F20.19 Emergency run torque limited
70.0 - 200.0 [100.0%]
6.3
Group Y: Manufacturer Function Parameters
The Group y is the manufacturer parameters group for commissioning at the factory before delivery.