Gndfi
8
g
In an I/O network, all I-fan units must have a unique address.
Analogue control
I/O
address
DIP 1 DIP 2 DIP 3 DIP 4 DIP 5 DIP 6
DIP 7 DIP 8
0
ON
ON
ON
ON
ON
ON: 10-0V dc
(10V=0%,
0V=100%)
OFF: 0-10V dc
(0V=0%,
10V=100%)
ON
N/A (ON/OFF)
Digital control
I/O
address
DIP 1 DIP 2 DIP 3 DIP 4 DIP 5 DIP 6
DIP 7 DIP 8
1
OFF
ON
ON
ON
ON
ON: 10-0V dc
(10V=0%,
0V=100%)
OFF: 0-10V dc
(0V=0%,
10V=100%)
ON
ON: 50%
OFF: 100%
2
ON
OFF
ON
ON
ON
3
OFF
OFF
ON
ON
ON
4
ON
ON
OFF
ON
ON
5
OFF
ON
OFF
ON
ON
6
ON
OFF
OFF
ON
ON
7
OFF
OFF
OFF
ON
ON
8
ON
ON
ON
OFF
ON
9
OFF
ON
ON
OFF
ON
10
ON
OFF
ON
OFF
ON
11
OFF
OFF
ON
OFF
ON
12
ON
ON
OFF
OFF
ON
13
OFF
ON
OFF
OFF
ON
14
ON
OFF
OFF
OFF
ON
15
OFF
OFF
OFF
OFF
ON
16
ON
ON
ON
ON
OFF
17
OFF
ON
ON
ON
OFF
18
ON
OFF
ON
ON
OFF