Gnd
16
g
Mains power supply
Mains voltage
1-phase: 230Vac (-10%, +6%)
3-phase: 400Vac (-10%, +6%)
Mains frequency
50/60 Hz
Max. power consumption electronics
5W
Inputs
Analog In
Voltage- or temperature measuring
Voltage 0-10V, temperature sensor
type S7 (-50°C to 110°C)
I/O-net
I/O-net
PF (PowerFail)
Make-contact
Position feedback actuator
Potentiometer 4k7Ω (+/- 20%) or CPS
Limit switches
30Vac / 60Vdc , max 1A
Outputs
Relay (2x)
1-phase: 240Vac, max 4A
3-phase: 400Vac, max 4A
Manual control
Rotary switch
Closed
– 0 – A – 0 - Open
Housing
Plastic housing with screw-on lid
IP54
Dimensions (lxwxh)
300x240x140mm
Weight (unpacked)
1-phase: 1,92 kg
3-hpase: 2,28 kg
Ambient climate
Operating temperature range
0°C to +40°C / 32°F to 104°F
Storage temperature range
–10°C to 50°C / 14°F to 122°F
Relative humidity
< 95%, uncondensed
I/O-network
Possibility of communication via the I/O-network. One control computer and a maximum of 31 network modules
may be connected to the I/Onetwork. Each connected network module has a unique address. After an address
has been changed, the network module should always be restarted (power off-on).
Output / input type
Output type
IMS address sequence number
Air inlet position
"IMS address".01
Input type
Analogue measurement (temp.)
"IMS address".01
Air inlet position measurement
"IMS address".02