Lumina 38

 

System 

 

 

 

21 

 

 

 

 

SYSTEM

 

 

 

 

 

SYSTEM

 

 

SYSTEM 

 tab page 

Common

 

 

 

Clock type

 

Setting of the 12 or 24 hour time indication. 

Time and Date

 

Setting of the current time and date 

Computer name

 

Setting of the name of the control computer. 

Computer number

 

Setting of the sequence number of the control computer in the network.   

Language

 

Setting of the program language. 

S2S MasterSlave

 

Master/Slave setting. If the control computer is included in a network, only one control 
computer in the network must be set as 

MASTER

. Set all the other control computers 

as 

SLAVE

   

 

 

Summary of Contents for LUMINA 38

Page 1: ...g...

Page 2: ...duced by Fancom For the latest information about product installation and operation please contact the customer service dept and or the technical service dept of the Fancom concerned In spite of the c...

Page 3: ...20 4 System 21 4 1 System 21 4 2 SD Card Menu 23 4 3 Application 24 4 4 Communication 25 4 5 IO Test 27 5 House setup 28 5 1 House setup 28 6 Installer 34 6 1 Ventilation 34 6 2 Heating cooling and h...

Page 4: ...Lumina 38 Table of contents ii 10 4 FRM 8 59 10 5 Connection FNet and I O net 60 11 Appendix EC declaration of conformity 61...

Page 5: ...nual also applies to other control computers in the Fancom F2000 line Always read the safety instructions and warnings carefully before using the control computer Always keep this manual close to the...

Page 6: ...rvice Center Virtually all Fancom equipment can be controlled and managed from a central location This requires the F Central FarmManager software package and a communication module The screens in the...

Page 7: ...le page 5 The ventilation is controlled based on the house temperature The purpose is to control the temperature as close as possible to a certain setpoint Minimum ventilation is always required in th...

Page 8: ...With length ventilation the air enters the house from both sides and is exhausted via end wall ventilation The control computer can control controllable fans and extra fans Controllable fans can be co...

Page 9: ...ontrollable fan Directly controlled by the A or by the relay R Extra fans can only be switched on or off via a relay They are usually used when the controllable fans are running at maximum or in combi...

Page 10: ...0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 The combi table also contains the ventilation capacity This is used to determine the ventilation position if control is based on ventilation capacity per hour per...

Page 11: ...Contr Extra fans deactivated One Exhaust relay fan activated Air inlets 21 open Tunnel inlets Do not use Example Settings between two positions The required ventilation level is 28 This percentage is...

Page 12: ...1 1 1 1 1 1 0 0 100 0 180000 T5 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 T6 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 T7 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 T8 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 T9 0 0 0 0 0 0...

Page 13: ...ill the modulation percentage Air inlet control depends on the settings The control computer can open the air inlets 30 midway between positions M3 and M4 The inlet position can also be modulated betw...

Page 14: ...that the switch off moment and cycle time can vary Example Optimum modulating control 1 Optimum ON time 2 minutes Maximum cycle time 10 minutes Modulate below 30 Control value ventilation 15 If the c...

Page 15: ...used in combination with variable speed fans of I Fans The setting Modulating below is used to make the setting where the controller switches from variable speed control towards modulating control an...

Page 16: ...temperature must be entered in the curve This may be necessary if floor heating is controlled based on temperature In this case the sensor measures a different temperature to the actual house tempera...

Page 17: ...ting is continuously on if the temperature of the heating control is lower than Setpoint hysteresis The heating is continuously off if the temperature is equal to or higher than the Setpoint Heating i...

Page 18: ...control a cooling unit Enter to which analog inputs the temperature sensor s have been connected and to which relay the cooling has been assigned Also enter the type of relay control ON OFF or MODULA...

Page 19: ...humidity control can only activate if a humidity setpoint has been set Enter to which relay the humidity control has been assigned Also enter the type of relay control ON OFF or MODULATING See also Se...

Page 20: ...ity sensor is adjusted The effect of the HumiTemp correction is controlled by the next settings The age factor tells how the HumiTemp should adapt in relation to the age of animals This means there is...

Page 21: ...temperature will be smaller The control computer regularly checks the house temperature If this is below the setpoint house temperature the offset heating will be gradually lowered At the same time it...

Page 22: ...etc Never mount the Lumina 38 in a humid and or dusty room and certainly not in the room where the animals are present Mount the Lumina 38 at such a height that you can control the Lumina 38 easily e...

Page 23: ...ins voltage and frequency for which this Fancom controller is suitable see chapter Technical Specifications in this manual correspond to the mains voltage and frequency on site Be sure that the Lumina...

Page 24: ...lation heating cooling and humidification 4 Clocks registration and external alarms Settings of the clocks input for external registration and outside climate 5 External alarms Setting of external ala...

Page 25: ...r name Setting of the name of the control computer Computer number Setting of the sequence number of the control computer in the network Language Setting of the program language S2S MasterSlave Master...

Page 26: ...mbers Enter code 1111 to deactivate the password protection When the correct password has been entered all user screens can be accessed The system will request the password again if the controller is...

Page 27: ...aring animal data The house section number is additional to the computer number The set data and the operating program in the control computer can be transferred to an SD card This data can be copied...

Page 28: ...ter to the SD card Update FUNC Update FUNC loads an operating system type FIN from the SD card onto the control computer Select the required file using the en keys on the alpha numeric keyboard Confir...

Page 29: ...ection for intelligent network modules For example Intelligent Relay Modules IRM Intelligent Digital Modules IDM or Intelligent Sensor Modules ISM SYSTEM COMMUNICATION tab page IO Net Reset counters S...

Page 30: ...ers Setting used to reset all data to zero simultaneously If there is no S2S communication the Receive and Transmit counters should be set to 0 Tab page Slaves shows the connected I2C modules and IO N...

Page 31: ...est menu inputs can be readout and outputs controlled at system level SYSTEM IO TEST The functions in the IO test menu stop all the control actions of the control computer Only use this to quickly tes...

Page 32: ...ment Setting indicating if RH measurement is used If RH measurement is used the RH influence on heating cooling and ventilation can be used Humidification Setting indicating if humidity control is use...

Page 33: ...er of controls HOUSE SETUP tab page Combi M MT part Setting indicating if the controllable part of the ventilation control consists of linear controllable fans LINEAR or modulating on off fans RELAY A...

Page 34: ...The desert control can be used to enable the tunnel inlets in minimum ventilation By using this setting coolpads can be used earlier in the combi table to cool the air This is energy efficient and wi...

Page 35: ...g if HumiTemp is to be used to correct the house temperature Data linked to animals Setting indicating that clocks are only to be controlled if there are animals in the house The control computer will...

Page 36: ...ion is permitted Early Normal Late Min Correctie Setting of the allowed maximum compensation below the average house temperature Tiny Small Average Large Huge Max Correctie Setting of the allowed maxi...

Page 37: ...se the correction when the actual house temperature has been below the setpoint house temperature for an uninterrupted period of 2 hours If the actual house temperature briefly comes above the setpoin...

Page 38: ...ee Combi table page 5 All the positions in the combi table must be fully entered The screens for the M MT phase are explained below The same screen explanation applies to the T phase INSTALLER VENTILA...

Page 39: ...off 1 fan on M modulating fan This option is only possible if modulating fans are used INSTALLER VENTILATION COMBI MTT M MT phase min tab page Inlet Position Setting of the ventilation percentage at w...

Page 40: ...all positions used If ventilation is used in m3 hour animal always fill in this column INSTALLER VENTILATION COMBI MTT M MT phase min tab page Warm Position Setting of the ventilation percentage at w...

Page 41: ...house Combi control Setting of the speed of progression to the next or previous position in the combi table Choose from SLOW MODERATE FAST Select SLOW if the transitions follow too quickly in successi...

Page 42: ...e lee side of the house If the wind comes from this direction positions under wind side the ventilation control may be influenced Modulating Setting indicating the required modulation type NONE OPTIMA...

Page 43: ...a cycle ON plus OFF period Calc ON OFF Time Readout of the actual ON OFF time Modulating Micro control Modulate below Setting of the ventilation percentage below which the control computer will apply...

Page 44: ...relay addresses Rotate Setting indicating if fans controlled by the combi relays rotate in a certain sequence INSTALLER VENTILATION SETTINGS tab page Imago Description Setting of the name of the func...

Page 45: ...uired position before the fans activate Modulate link Setting indicating if these air inlets are to be included in modulating ventilation if modulating ventilation is used Position wind side Setting o...

Page 46: ...ass positions which represent the lee side of the house If the wind comes from this direction positions under wind side the ventilation control may be influenced INSTALLER HEATING Description Setting...

Page 47: ...Output address Setting of the analog output address choice LINEAR control or relay output choice RELAY control Relay type Setting of the type of relay control ON OFF Modulating Evaporative cooling Set...

Page 48: ...ED Description Setting of the name of the function Time clock type Setting indicating how the user can use the clock ON OFF User enters on off times ON DURATION User enters time and duration of activa...

Page 49: ...the clock ON OFF User enters on off times ON DURATION User enters time and duration of activation Registration via For the central clock Setting of the registration input used to measure the amount o...

Page 50: ...e user can use the clock ON OFF User enters on off times ON DURATION User enters time and duration of activation INTERMIT Intermittent repeat clock An intermittent light clock can be used to periodica...

Page 51: ...to control the light intensity in percentages Analog type Setting indicating the analog control type Reaction speed Setting of the reaction speed of the light sensor that controls light intensity if t...

Page 52: ...e This option is only available if Display AMOUNT only with measurement type CONTACT Display amount Setting how the unit is displayed AMOUNT number units per minute Amount per min TIME the time the co...

Page 53: ...Measurement outside temp Setting if the control computer carries out outside measurement concerned itself INT or via the communication network COMM Only enter the address of the input if INT is selec...

Page 54: ...fault BLACK_4P BLACK_2P DAVIS PA2 By choosing the required type and assigning the correct inputs the control computer will automatically make all corresponding settings Input wind vane Setting the add...

Page 55: ...put type Setting of the passive not controlled input status N O CONTACT normally open if it makes no contact N C CONTACT normally closed if it makes contact iPRODUCTS to receive alarms from an intelli...

Page 56: ...n 2 minutes The control computer monitors to that effect the current house temperature every 30 seconds and compares it with the values of the last 2 minutes In addition to the alarm relay the control...

Page 57: ...ontrolled relay status N O normally open if it makes no contact N C normally closed if it makes contact Alarm type Setting for the way in which the alarm will be processed LOUD Loud alarm switch the a...

Page 58: ...e setting possibilities per type or input or output The address of the chosen connection must be entered at various places in the system settings An input or output address consists of two parts separ...

Page 59: ...ress The address of the output Channel type Shows the type of analog output Channel function Setting of the type of analog control 0 10V 10 0V Correction factor Factor to determine the adjustment of t...

Page 60: ...E ON OFF MODULATING OPEN O CLOSE LINKED Channel function Setting of the type of digital control DIRECT HEATING COOLING Hysteresis With an on off control this is the switch difference of the relay cont...

Page 61: ...Digital inputs DI Open contact voltage 12Vdc Low level 1 0Vdc Application Counter input min pulse width 25mSec Max frequency 20Hz Application Frequency input Max frequency 5kHz 16 Digital outputs DO 1...

Page 62: ...Lumina 38 Technical specifications 58 1 Touch screen 2 HI mainboard 3 SBC 4 LED strip 5 FUNC CPU 6 IOB 12 I O 7 Power supply 8 Internal relays 2x FRM 8...

Page 63: ...Lumina 38 Technical specifications 59 AI type Type analog input Voltage measurement U Resistance measurement R AO 6 Analog outputs AI 12 Analog inputs DI 8 Digital inputs DO 2 8 digital outputs...

Page 64: ...or Example Setting the I O net terminal resistor 1 One control computer connected to two I 0 network modules using one I O net The control computer is located between the two I O network modules This...

Page 65: ...lace Panningen the Netherlands Hereby declares that Lumina 38 Satisfies the conditions of 1 The Low Voltage Directive 2014 35 EU according to EN 61010 2 the EMC Guideline directive 2014 30 EU Emission...

Reviews: