Lumina 38
House setup
29
HOUSE SETUP
→
tab page
Outside
Measurement outside
temp.
Setting indicating if outside temperature measurement is used. If outside temperature
measurement is used the outside temperature can influence a number of controls.
Measurement outside
RH
Setting indicating if outside RH measurement is used. Using absolute moisture
calculation, the control computer determines if the outside air is suitable for
dehumidification.
Measurement wind
Setting indicating if wind direction and wind speed measurement is used. If wind
direction and wind speed measurement is used the wind can influence a number of
controls.
HOUSE SETUP
→
tab page
Combi
M/MT-part
Setting indicating if the controllable part of the ventilation control consists of linear
controllable fans (
LINEAR
) or modulating on/off fans (
RELAY
).
Analog extra additional
Setting indicating the number of analog (linear controllable) groups that you want to
activate as extra fans in the controllable part (only if
LINEAR
has been chosen at
M/MT-
part
).
Relay extra additional
Setting indicating the number of groups, switched by a relay that you want to activate as
extra fans in the controllable part (only if
LINEAR
has been chosen at
M/MT-part
).
Vortex damper in use
Setting indicating if vortex damper control is used. A vortex damper is always controlled
analog. There is one vortex damper control per extra switched fan. (only if
LINEAR
has
been chosen at
M/MT-part
)