Lumina 38
Installer
36
INSTALLER
→
VENTILATION
→
COMBI MTT
→
M/MT-phase(min)
→
tab page
Cap.
Position %
Setting of the ventilation percentage at which fans should activate/deactivate and air
inlets open/close. The ventilation percentages must increase from the lowest to the
highest position.
Pressure Pa
*
Setting of the required pressure for the corresponding position. A rule of thumb: the
higher the ventilation position, the lower the required pressure. Enter 0 to deactivate
pressure control.
Cap. m3/h
Setting of the ventilation capacity (m3/hour) for all positions used. If ventilation is used
in m3/hour/animal, always fill in this column!
INSTALLER
→
VENTILATION
→
COMBI MTT
→
M/MT-phase(min)
→
tab page
Warm
Position %
Setting of the ventilation percentage at which fans should activate/deactivate and air
inlets open/close. The ventilation percentages must increase from the lowest to the
highest position.
Inlet %
Setting of the required inlet positions.
Tunnel %
Setting of the required inlet positions. (If the tunnel inlet is not used, you may enter the
summer inlet position at tunnel inlet position.)
Pressure Pa
Setting of the required pressure for the corresponding position. A rule of thumb: the
higher the ventilation position, the lower the required pressure. Enter 0 to deactivate
pressure control.