- 3 -
1. Switch off power supply.
2. Install indicator on DIN rail.
3. Connect the indicator according to the connection diagram:
4. Connect the power supply of the indicator (230 V AC) to termi-
nals 5 and 6; connect the current transformer output to termi-
nals 1-7 (phase L1), 2-8 (phase L2), 3-9 (phase L3).
5. Switch on the power supply.
If the secondary windings of the measuring transformers
are open (e.g. during assembly) and a current flows thro-
ugh the measured circuit, a dangerous voltage may be
induced at the terminals of the measuring transformer.
It is absolutely necessary to protect oneself from such a
situation by switching off the power supply of measured
circuits or installing additional bridges short-circuiting
the secondary side of a measuring transformer.
The indicator is designed for current measurement using
current transformers with a rated output current of 5 A.
Current flow through the measuring circuit of the indi-
cator of a value higher than 6 A may lead to damage of
the indicator.
For increased safety, it is recommended that one side
of the current transformer be earthed as shown in the
connection diagram.