1. Press and hold down the SET button located on the facade of 

the indicator.

2. Release the button after a minimum of 5 seconds.

3. Use successive short presses of the SET button to set the de-

sired current ratio value.

4. Confirmation of the change takes place by pressing the SET 

button for a minimum of 5 seconds.

The set value of the current ratio is indicated each time 

on the display of the indicator when the power is swit-

ched on.

power supply 

165÷265 V AC/DC

measurement 

indirect (transformer 5 A)

number of measurement channels 

3

measured value 

TrueRMS value AC current

frequency 

45÷55 Hz

maximum current 

6 A

measurement range 

0÷5 A

maximum momentary overload 

20 A/1 s

indication accuracy 

1%

reading accuracy

measurement range  <100 A 

0.1 A

measurement range ≥100 A 

1 A

display (for 1 phase) 

3×LED segment 6×10 mm

power consumption 

4 W

Current ratio programming

Technical data