background image

108

2.2

 Current setting

 

,

B

2.3

 Underload by cos 

 

. PF.

e.g.: relay GL16

,

B

 

=8+4 =12 A

21

)8//

/2$'

&855(17
6(77,

1*

,

%

 

$

 

75,3&/$666

RQ

RII

56

7

W

R

21

21

,

,

x n

Installation and Adjustment guide

Relays C, GL, P, PF, G, BG and GEN

Adjust the current 

,

B

 on the corresponding dipswitches (full load current). 

When setting the current take into account that the base current of the relay 
always remains added to the current selected with the dipswitches in “ON”  
position (to the right). The total addition is the set current 

,

B

.

Overload tripping current from 1,1 x 

,

B

a)  For motor or generator rated currents (

,

N

) within the range of the relay, the 

setting 

,

B

 must be equal to the  

,

N

 of the motor or generator.

,

,

N

b)  For motor rated currents below the range of the relay, the setting 

,

B

 must 

be equal to the rated current of the motor 

,

N

 multiplied by the number 

of times that the conductors have been passed through the relay holes.

c)  For motor or generator rated currents (

,

N

) above the range of the relay, use 

three current transformers .../5 in combination with the C9, GL16, P19, 
PF16-R, G17, BG17 or GEN10 according to application.

     With current transformers it is always a must to pass the conductors 2 

times or more through the holes of the relay.

PS relay

This adjustment is to be made according to the nominal current of the motor 

,

N

 indicated in its characteristics plate. The value to be set 

,

B

 is the same as 

,

N

. The relay trips with overloads above 1,1 x IB 

,

B

.

,

B

=  

,

N

The cos 

 

 underload trip level is set by means of a potentiometer with 

settings from 0,15 to 1,0.

Select this value taking into consideration the no-load motor cos 

 

 and 

that corresponding to the estimated minimum operating load. Choose an 
intermediate value between these two cos 

 

 levels and set it  in the relay.

Select the underload trip delay from 5 to 45 seconds using the 3 
corresponding dipswitches (trip delay).

For your guidance you can find two practical examples below.

a)  A very oversized motor for its application. The cos 

 

 of the motor is 0,15 

when working without load.

b)  A slightly oversized motor for its application. The cos 

 

 of the motor is 

0,25 when working without load.

If the above mentioned cos 

 

 values are unknown, the underload trip setting 

can be made in the following way:

1.  Set the underload trip delay to zero by moving the three dipswitches 

to the left (trip delay).

2.  Using the potentiometer (cos 

 

 setting), set the cos 

 

 value to the 

minimum: 0,15.

3.  Set the reset time to the minimum value using the potentiometer 

(cos 

 

 reset time).

4.  Start up the motor and run it with the minimum estimated load.

5.  Slowly turn the cos 

 

 potentiometer clockwise until the relay trips and 

the cos 

 

 LED lights up.

6.  Turn the cos 

 

 potentiometer anticlockwise until the cos 

 

 is set at 

approximately 30% less than the previous value (point 5).

7.  Set the underload trip delay using the 3 corresponding dip switches. 

Set the reset time using the adequate potentiometer.

Nominal
load

Estimated
minimum load

Approximated 

cos

 

 

adjustement area

cos

 

 

No-load

Nominal
load

Estimated
minimum load

Approximated 

cos

 

 

adjustement area

cos

 

 

No-load

always n ≥ 2

,

B

=

  

,

N

  

motor   

x 5 x n

       

,

N

  

trafo 

Summary of Contents for C 9

Page 1: ...ed as a model of the thermal image of the motor and is continously compared to the values set on the relay The three power supply cables to the motor are not directly connected to the relay but pass t...

Page 2: ...igh current busbars In star delta starting the relay or the current transformers must be installed between the fuses or circuit breaker and the contactor Relays used in combination with frequency inve...

Page 3: ...B use the corresponding dip switches The recommended values are listed in the following tables Average trip curves IEC 947 4 1 Cold curve represents the performance of the relay without any previous c...

Page 4: ...ad trip level is set by means of a potentiometer with settings from 0 15 to 1 0 Select this value taking into consideration the no load motor cos and that corresponding to the estimated minimum operat...

Page 5: ...ng three dipswitches To avoid nuisance trips set this level to approximately 10 above the no load motor current Example 2 5 Phase sequence Monitoring the current GL and P relays An incorrect phase seq...

Page 6: ...ble pumps in service stations and water pumping surface pumps etc Compressors Fans blowers and ventilators Industrial refrigeration and air conditioning Centrifuges Presses Cranes elevators escalators...

Page 7: ...400 V 50Hz 2 0 2 8 3 8 5 5 7 9 5 13 16 5 24 32 40 47 64 79 92 113 149 183 220 440 460 V 60Hz 1 9 2 5 3 4 4 8 6 7 5 11 15 21 27 33 39 53 65 79 95 120 153 183 MODELS Adjustment range B A MOTOR CHARACTE...

Reviews: