background image

109

2.4

 Undercurrent.

Single phase relay PS

The setting of the underload trip level is made using a potentiometer in wich 

a factor between 0,4 and 0,9 is to be chosen. By multiplying this factor by 

the adjusted 

,

B

  

we obtain a current value under which the relay will trip and 

disconnect the motor. The trip is delayed by 5 seconds.

a)  If the value of the 

,

B

 of the motor without load is known: 

•   To avoid unwanted trips it is recommended to adjust the value 15% 

above the 

,

B

 of the motor without load.

Example:

b)   If the value of the 

,

B

 of the motor without load is unknown:

•  If the pump is adequately dimensioned, the recommended value for 

this factor is 0,7. Adjust the potentiometer “undercurrent” to 0,7.

•     If the pump is excessively dimensioned, and during its operation 

unwanted trips could occur, the underload adjusted factor should be 

reduced to approximately 0,6.

Three phase relay P

The undercurrent trip level in P relays is set using three dipswitches. To 

avoid nuisance trips, set this level to approximately 10% above the no-load 
motor current.

   Example:

2.5

 Phase sequence

Monitoring the current. GL and P relays

An incorrect phase sequence is detected by current sensing and it is only 

operative during the motor start-up. For correct detection the starting time 

must be longer than 0.2 s.

In GL relays the user can activate or desactivate this protection by means 

of a dipswitch. Should the right phase sequence be critical, move the 

dipswitch to the “ON” position. If this protection is not required, always leave 

it in the “OFF” position.

As this function is not compatible with the use of frequency inverters, where 

it is necessary to protect phase sequence in these installations, move the 
dipswitch to “OFF” and install the Fanox “S” model relay.

Monitoring the voltage. PF relays

An incorrect phase sequence is detected by voltage monitoring.

In the event that an incorrect phase sequence has been detected, the 

motor will not start-up since the relay has tripped because of previously 

detecting the wrong phase sequence.

• Dry running

• Dry running

0.6 x 1.1 = 0.66

x1.1

Summary of Contents for C 9

Page 1: ...ed as a model of the thermal image of the motor and is continously compared to the values set on the relay The three power supply cables to the motor are not directly connected to the relay but pass t...

Page 2: ...igh current busbars In star delta starting the relay or the current transformers must be installed between the fuses or circuit breaker and the contactor Relays used in combination with frequency inve...

Page 3: ...B use the corresponding dip switches The recommended values are listed in the following tables Average trip curves IEC 947 4 1 Cold curve represents the performance of the relay without any previous c...

Page 4: ...ad trip level is set by means of a potentiometer with settings from 0 15 to 1 0 Select this value taking into consideration the no load motor cos and that corresponding to the estimated minimum operat...

Page 5: ...ng three dipswitches To avoid nuisance trips set this level to approximately 10 above the no load motor current Example 2 5 Phase sequence Monitoring the current GL and P relays An incorrect phase seq...

Page 6: ...ble pumps in service stations and water pumping surface pumps etc Compressors Fans blowers and ventilators Industrial refrigeration and air conditioning Centrifuges Presses Cranes elevators escalators...

Page 7: ...400 V 50Hz 2 0 2 8 3 8 5 5 7 9 5 13 16 5 24 32 40 47 64 79 92 113 149 183 220 440 460 V 60Hz 1 9 2 5 3 4 4 8 6 7 5 11 15 21 27 33 39 53 65 79 95 120 153 183 MODELS Adjustment range B A MOTOR CHARACTE...

Reviews: