Rev. 07
74/138
CLP (*)
Function Enable: Yes/No
Settings group: 1 to 4 (step 1)
No load Time: 0.02 to 300 s (step 0.01 s)
Cold load Time: 0.02 to 300 s (step 0.01 s)
CLP activation threshold: 60 mA
CLP reset threshold: 80 mA
50BF (*)
Function Enable: Yes/No
Time Delay: 0.02 to 1.00 s (step 0.01 s)
Open circuit breaker activation threshold: 60 mA
Programmable logic
control (PGC)
OR4, OR4_LATCH, OR4_PULSES, OR4_TIMERUP, OR4_PULSE, NOR4,
NOR4_TIMERUP, NOR4_PULSE, NOR4_PULSES, AND4, AND4_PULSES,
AND4_TIMERUP, AND4_PULSE, AND4_LATCH, NAND4, NAND4_TIMERUP,
NAND4_PULSE.
Trip output
24 Vdc; 135 mJ (activation of the striker or low powered coil)
Signaling outputs
3 configurable outputs (output 1, output 2 and output 3):
220 Vdc
– 8 A
250 Vac
– 8 A
Signaling inputs
3 inputs: they are activated by short-circuiting the terminals without external supply.
Frequency
50/60Hz
Current measurement
Fundamental values (DFT)
Sampling: 16 samples/cycle
±2% in a band of ± 20% the nominal current and ±4% or ± 5 mA in the rest of the band.
Events
1024 events
Disturbance Fault
Recording (DFR)
20 fault reports, 16 events in each
10 disturbance records in COMTRADE format (50 cycles each)
Load Data Profiling
(Current Demand)
Demand of current with the following characteristics:
•
Number of records: 168
•
Recording mode circular
•
Sampling rate (interval): configurable through communications: 1
– 60
min
•
Record format:
Date/Time
IMAX (in interval)
IMAX (actual)
IA; IB; IC; IN
Summary of Contents for SIA-B Series
Page 8: ...www fanox com Rev 07 8 138 Cut out pattern 2 3 Striker dimensions 2 3 1 PRT 15...
Page 9: ...www fanox com Rev 07 9 138 2 3 2 PRT A 44 5 B 49 5 C 56 5 D 64 5 E 42 5...
Page 10: ...www fanox com Rev 07 10 138 2 4 Connection diagram NOTE STRIKER 6 24 Vdc 0 135 W s...
Page 28: ...www fanox com Rev 07 28 138...
Page 35: ...www fanox com Rev 07 35 138...
Page 36: ...www fanox com Rev 07 36 138...
Page 37: ...www fanox com Rev 07 37 138...
Page 38: ...www fanox com Rev 07 38 138...
Page 40: ...www fanox com Rev 07 40 138...
Page 41: ...www fanox com Rev 07 41 138...
Page 42: ...www fanox com Rev 07 42 138...
Page 76: ...www fanox com Rev 07 76 138 6 3 Standards...
Page 77: ...www fanox com Rev 07 77 138...
Page 137: ...www fanox com Rev 07 137 138 NOTES...
Page 138: ...www fanox com Rev 07 138 138...