9.
COMMISSIONING
It is recommended that the following safety measures are taken before starting up the facility for
the first time, or after a trip event:
•
FANOX recommends the use of the KITCOM accessory with a battery in the front port.
This additional energy source allows the relay to be monitored and the trip to function
without the need for self-power in any breakdown situation.
•
Once all of the connections have been made, we recommend a check to make sure that
they are correct, safe and well attached.
•
The "complete test" menu procedure should be applied.
NOTE! See 6.9.
•
It is important to check that the measurements are correct once the facility has been
powered up.
Maintenance
:
FANOX recommends a minimum of one facility inspection per year, to at least go
through the test menu and check the values of the measurements.
9.1.
Checklist for Commissioning
The commissioning sheets that are needed to register the commissioning process and the specific
settings for each installed piece of equipment are found in the Appendix
.
9.2.
Electrostatic discharge
Before handling any of the equipment electronic components, make sure that you have read the
section of the user manual related to electrostatic discharges.
9.3.
Visual Inspection
Make sure that the cabling has been installed as per the external connection diagrams.
9.4.
Earthing
It is very important for the equipment to be earthed correctly. To check this, make sure that the
equipment earth connection, located on the reverse side of the relay, is correctly connected to the
facility local earth connection.
9.5.
Current transformers
The high voltage that is generated in the secondary circuits of current transformers can cause
death and could damage the facility. Therefore, the secondary circuits of current transformers
should never be opened.
Summary of Contents for SIA-B
Page 9: ...www fanox com Rev 32 9 114 The dimensions are in mm Cut out pattern ...
Page 11: ...www fanox com Rev 32 11 114 Cut out pattern 2 3 Striker dimensions 2 3 1 PRT 15 ...
Page 12: ...www fanox com Rev 32 12 114 2 3 2 PRT A 44 5 B 49 5 C 56 5 D 64 5 E 42 5 ...
Page 19: ...www fanox com Rev 32 19 114 3 3 Functional Diagram ...
Page 24: ...www fanox com Rev 32 24 114 Dimensions ...
Page 27: ...www fanox com Rev 32 27 114 Dimensions Model CT16 5 Model CT08 5 ...
Page 42: ...www fanox com Rev 32 42 114 ...
Page 43: ...www fanox com Rev 32 43 114 ...
Page 44: ...www fanox com Rev 32 44 114 ...
Page 45: ...www fanox com Rev 32 45 114 ...
Page 47: ...www fanox com Rev 32 47 114 ...
Page 48: ...www fanox com Rev 32 48 114 ...
Page 49: ...www fanox com Rev 32 49 114 ...
Page 101: ...www fanox com Rev 32 101 114 Trip Voltage Level 17 Vdc C Nominal current 8 C CT type CT008 ...
Page 113: ...www fanox com Rev 32 113 114 NOTES ...
Page 114: ...www fanox com Rev 32 114 114 ...