Rev. 32
68/114
Function
50/51N
Function Enable: Yes/No
Current Tap: 0.20 to 7 x Is (step 0.01)
Curves: IEC 60255-151 and IEEE
Curve Type: IEC Inverse curve, IEC very inverse curve, IEC extremely inverse curve
IEC long time inverse, IEEE Inverse curve, IEEE very inverse curve, IEEE extremely
inverse curve.
Time delay: 0.05 to 300 s (step 0.01 s)
Time Dial (TMS): 0.05 to 1.25 (step 0.01)
Curve, activation level 110%
Curve, deactivation level 100%
Defined time, activation level 100%
Defined time, deactivation level 90%
Instantaneous deactivation
Timing accuracy: 5% or 40 ms (greater of both, considering the Time Delay is
influenced by the used CT)
Function
49T (*)
External trip. Charging time 7 seconds
Function
49 (*)
Function Enable: Yes/No
Current Tap: 0.10 to 2.40 Is (step 0.01)
ζ heating: 3 to 600 minutes (step 1 min)
ζ cooling: 1 a 6 x ζ heating (step 1)
Alarm level: 20 a 99% (step 1 %)
Trip level: 100%
Trip reset: 95% of alarm level
Timing accuracy: ± 5% regarding theoretical value
Trip Block (*)
Blocking: Yes/No
Blocking limit: 1.5 to 20 x In (step 0.01)
Programmable logic
control (PLC)
OR4, OR4_LATCH, OR4_PULSES, OR4_TIMERUP, OR4_PULSE, NOR4,
NOR4_TIMERUP, NOR4_PULSE, NOR4_PULSES, AND4, AND4_PULSES,
AND4_TIMERUP, AND4_PULSE, AND4_LATCH, NAND4, NAND4_TIMERUP,
NAND4_PULSE.
Trip output
24 Vdc; 135 mJ (activation of the striker or low powered coil)
Signalling outputs (*)
2 configurable outputs (output 2 and output 3):
220 Vdc
– 8 A (30 W max)
250 Vac
– 8 A (62,5 VA max)
Frequency
50/60Hz
Summary of Contents for SIA-B
Page 9: ...www fanox com Rev 32 9 114 The dimensions are in mm Cut out pattern ...
Page 11: ...www fanox com Rev 32 11 114 Cut out pattern 2 3 Striker dimensions 2 3 1 PRT 15 ...
Page 12: ...www fanox com Rev 32 12 114 2 3 2 PRT A 44 5 B 49 5 C 56 5 D 64 5 E 42 5 ...
Page 19: ...www fanox com Rev 32 19 114 3 3 Functional Diagram ...
Page 24: ...www fanox com Rev 32 24 114 Dimensions ...
Page 27: ...www fanox com Rev 32 27 114 Dimensions Model CT16 5 Model CT08 5 ...
Page 42: ...www fanox com Rev 32 42 114 ...
Page 43: ...www fanox com Rev 32 43 114 ...
Page 44: ...www fanox com Rev 32 44 114 ...
Page 45: ...www fanox com Rev 32 45 114 ...
Page 47: ...www fanox com Rev 32 47 114 ...
Page 48: ...www fanox com Rev 32 48 114 ...
Page 49: ...www fanox com Rev 32 49 114 ...
Page 101: ...www fanox com Rev 32 101 114 Trip Voltage Level 17 Vdc C Nominal current 8 C CT type CT008 ...
Page 113: ...www fanox com Rev 32 113 114 NOTES ...
Page 114: ...www fanox com Rev 32 114 114 ...