Rev.23
62/311
Synchronism function (25) associated to manual closure (52)
If “ 52 permission of closure” is associated with “Permission of closure” of synchronism function, could
be occur:
1. If permissions LLLB, DLLB, LLDB y DLDB of 25 function are all prohibited, the closure of the circuit
breaker
does not occur. In spite of “close breaker” command being execute by communication or
pressing the key in the relay, circuit breaker never will close
2. If LLLB, DLDB, DLLB, y LLDB permissions of 25 function are enable it can be distinguished some
possibilities:.
a) If line, bar or both of them are dead it will always produced the manual closure of the circuit
breaker
because “52 permission of closure” only depends on corresponding permission
adjustment, and it is not necessary synchronism to get the circuit breaker closure.
b) If both, line and bar, are alive it will be necessary to get the manual closure of the circuit
breaker, not only LLLB permission to be enable either to check synchronism. If LLLB
permission is enable but synchronism conditions do not verify, after pressing CLOSE
BREAKER command, circuit breaker closure does not occur and vice versa.
4.18. Cold Load Pickup
This unit is used to prevent undesired operations of the overcurrent functions in the cases where, when
the line is deenergised, all the loads enter at the same time.
This function settings are as follows:
Group
Description
Minimum
Maximum
Step
Unit
Default
CLP
Cold Load Pickup
Permission
-
-
Yes/No
-
No
50P_1 Multiplier
1
5
0.01
-
1
50P_2 Multiplier
1
5
0.01
-
1
67P_1 Multiplier
1
5
0.01
-
1
67P_2 Multiplier
1
5
0.01
1
50N/G_1 Multiplier
1
5
0.01
1
50N/G_2 Multiplier
1
5
0.01
-
1
67N_1 Multiplier
1
5
0.01
-
1
67N_2 Multiplier
1
5
0.01
-
1
CLP switch time
1
18000
0.01
s
15
CLP duration
1
18000
0.01
s
15
Summary of Contents for SIL B
Page 1: ...EN_FANOXTD_MANU_SIL_Feeder_SILB_R023 Docx USER S MANUAL SIL B Feeder Relay...
Page 8: ...www fanox com Rev 23 8 311 2 DIMENSIONS AND CONNECTION DIAGRAMS 2 1 Equipment front view...
Page 9: ...www fanox com Rev 23 9 311 2 2 Equipment dimensions...
Page 10: ...www fanox com Rev 23 10 311...
Page 11: ...www fanox com Rev 23 11 311 2 3 Cut out pattern CUT OUT PATTERN...
Page 12: ...www fanox com Rev 23 12 311 2 4 Connection diagrams Analog connections...
Page 13: ...www fanox com Rev 23 13 311...
Page 14: ...www fanox com Rev 23 14 311 Digital connections Outputs and Trip circuit supervision...
Page 15: ...www fanox com Rev 23 15 311 2 5 Terminals IEC 61850 or DNP3 0 protocols...
Page 17: ...www fanox com Rev 23 17 311 IEC 60870 5 103 protocol...
Page 25: ...www fanox com Rev 23 25 311 3 3 Functional diagram...
Page 28: ...www fanox com Rev 23 28 311 3 5 1 SIL B 1 CHARGE CURVE 3 5 2 SIL B 5 CHARGE CURVE...
Page 91: ...www fanox com Rev 23 91 311...
Page 140: ...www fanox com Rev 23 140 311...
Page 194: ...www fanox com Rev 23 194 311 Polarization V 35 0 V C Operating Angle 180 C Halfcone Angle 3 C...
Page 307: ...www fanox com Rev 23 307 311 50BF init Fault init 79 Closure permission 52 closure permission...
Page 310: ...www fanox com Rev 23 310 311 NOTES...
Page 311: ...www fanox com Rev 23 311 311...