Rev.06
17/226
Function
Description
SIL-D
Protection
50
Instantaneous phase overcurrent protection function
2
50N/G
Instantaneous neutral overcurrent protection function
2
50/51
Phase inverse time overcurrent protection function
1
67N
Inverse time directional neutral overcurrent protection function
2
67NI
Directional isolated neutral overcurrent protection function
2 (Optional)
79
Reclosing device
Up to 5 attempts
50BF
Breaker failure protection
1
74TCS
Trip circuit supervision
1 through configurable inputs
CLP
Cold load pickup
1
59N
Neutral overvoltage
1
Trip block
Trip block for switch disconnector
1
86
Trip Output Lockout
✓
49T
External trip
1 through configurable inputs
Circuit Breaker monitoring
52
Status and control of the circuit breaker
✓
Counter to record the number of openings
✓
Accumulated amps counter:
✓
Maximum openings in a time window
✓
Measurements
Phase and neutral rms currents with a precision of 2% in a band of
±20% when compared to the rated current, and 4% in the rest of
the range (IA, IB, IC, IN)
✓
Neutral voltage (VR)
✓
Angle between neutral voltage and neutral current
✓
Maximum current
✓
Summary of Contents for SIL-D00
Page 8: ...www fanox com Rev 06 8 226 2 DIMENSIONS AND CONNECTION DIAGRAMS 2 1 Equipment front view...
Page 9: ...www fanox com Rev 06 9 226 2 2 Equipment dimensions...
Page 10: ...www fanox com Rev 06 10 226 2 3 Cut out pattern...
Page 12: ...www fanox com Rev 06 12 226 Digital connections Only as an example...
Page 13: ...www fanox com Rev 06 13 226 2 5 Terminals...
Page 49: ...www fanox com Rev 06 49 226...
Page 50: ...www fanox com Rev 06 50 226...
Page 51: ...www fanox com Rev 06 51 226...
Page 52: ...www fanox com Rev 06 52 226...
Page 200: ...www fanox com Rev 06 200 226...
Page 225: ...www fanox com Rev 06 225 226 NOTES...
Page 226: ...www fanox com Rev 06 226 226...