Rev.06
21/226
3.5.
Phase CT and neutral CT selection
Model
Phase
nominal
current
Neutral nominal current
Phase range
Neutral range
SIL-D00
1 A or 5 A
Residual phase connection,
1A or 5A
0.1 -30 A or 0.5-150 A
0.2-30A or 1-150A
SIL-D0S
1 A or 5 A
Residual phase connection,
0.5A or 0.1A
0.1-30 A or 0.5-150 A
0.1-30 A or 0.5-150 A
or
0.01-3A or 0.05-15A
SIL-DS0
0.5A or 2.5A
Residual phase connection, 1A
or 5A
0.05-15 A or 0.25-75 A
0.05-15 A or 0.25-75 A
or
0.1-30 A or 0.5-150 A
SIL-DSS
0.5A or 2.5A
Residual phase connection,
0.5A or 0.1A
0.05-15 A or 0.25-75 A
0.05-15 A or 0.25-75 A
or
0.01-3A or 0.05-15A
To ensure the relay functions correctly, a suitable current transformer must be used. The load of
the relay’s own measurement circuits and the load on the cables that connect the CTs and the
relay must be taken into account.
ACCURACY
BURDEN
RELAYS
5P10
1,5 VA
SIL-D/1
5P20
1,5 VA
SIL-D/1
5P30
1,5 VA
SIL-D/1
5P10
1,5 VA
SIL-D/5
5P20
1,5 VA
SIL-D/5
5P30
1,5 VA
SIL-D/5
Voltage measurement range is from 2 to 65 V
Summary of Contents for SIL-D00
Page 8: ...www fanox com Rev 06 8 226 2 DIMENSIONS AND CONNECTION DIAGRAMS 2 1 Equipment front view...
Page 9: ...www fanox com Rev 06 9 226 2 2 Equipment dimensions...
Page 10: ...www fanox com Rev 06 10 226 2 3 Cut out pattern...
Page 12: ...www fanox com Rev 06 12 226 Digital connections Only as an example...
Page 13: ...www fanox com Rev 06 13 226 2 5 Terminals...
Page 49: ...www fanox com Rev 06 49 226...
Page 50: ...www fanox com Rev 06 50 226...
Page 51: ...www fanox com Rev 06 51 226...
Page 52: ...www fanox com Rev 06 52 226...
Page 200: ...www fanox com Rev 06 200 226...
Page 225: ...www fanox com Rev 06 225 226 NOTES...
Page 226: ...www fanox com Rev 06 226 226...