4.6. Function 59N. Definite-time neutral overvoltage
This protection function is adjusted using four parameters:
Function
Description
Minimum
Maximum
Step
Unit
Default
59N
Definite-time neutral overvoltage
Permission
-
-
Yes/No
-
No
Pickup
2.0
65.0
0.1
V
40.0
Time Delay
0,02
300,00
0.01
s
10.00
Reset time
0,02
300,00
0.01
s
0,20
The operating time is completely independent of the measured neutral voltage, such that should
the neutral voltage exceed the set value during the same amount of time or more than the set
one during operation time, the protection function acts (trips) and there it is not restored until the
measured value of the neutral voltage drops below the voltage set point during adjusting reset
time.
The function pick up occurs at 100% of the adjusted input and the dropout at 95%. The reset
type is temporized and reset time is adjusted with reset time parameter.
The accuracy of the Time delay is equal to the preset time ±30 ms or ±0.5%
Summary of Contents for SIL-D00
Page 8: ...www fanox com Rev 06 8 226 2 DIMENSIONS AND CONNECTION DIAGRAMS 2 1 Equipment front view...
Page 9: ...www fanox com Rev 06 9 226 2 2 Equipment dimensions...
Page 10: ...www fanox com Rev 06 10 226 2 3 Cut out pattern...
Page 12: ...www fanox com Rev 06 12 226 Digital connections Only as an example...
Page 13: ...www fanox com Rev 06 13 226 2 5 Terminals...
Page 49: ...www fanox com Rev 06 49 226...
Page 50: ...www fanox com Rev 06 50 226...
Page 51: ...www fanox com Rev 06 51 226...
Page 52: ...www fanox com Rev 06 52 226...
Page 200: ...www fanox com Rev 06 200 226...
Page 225: ...www fanox com Rev 06 225 226 NOTES...
Page 226: ...www fanox com Rev 06 226 226...