Rev.06
41/226
It must be possible to lock the recloser, particularly is maintenance tasks are carried out on the
substation. To this end there are various SIL-D locking and unlocking possibilities:
•
From the HMI
. There is a specific key marked 79, plus a specific signal led, allowing recloser
operation, locking or unlocking it. In order that the command related to the key can run, the
menu must be in standby mode.
•
From the HMI.
This command can be executed from the control menu.
•
From two pulse inputs.
If the substation is equipped with a conventional remote control, two
pulse signals are usually assigned, where one locks the recloser and the other locks it.
•
Via protocol.
This is performed via any means of communication. This is carried out as if it
were a control, and the normal conditions of any control must be met. For example, if we are
operating from the HMI, it is understood that the relay is in local mode, whereby if a
Lock/Unlock command is received via remote control this shall be ignored.
•
From a level input.
In this case the recloser monitors the status of the input. This may be of
use if the company has a handle with a key.
In the first four cases, the equipment stores the lock situation in the non-volatile memory, as the
last control must be know for a possible re-start.
The auto-recloser´s start up is shown in the following figure: There are two stable conditions
here, Standby and Lockout, the other conditions are transient.
Summary of Contents for SIL-D00
Page 8: ...www fanox com Rev 06 8 226 2 DIMENSIONS AND CONNECTION DIAGRAMS 2 1 Equipment front view...
Page 9: ...www fanox com Rev 06 9 226 2 2 Equipment dimensions...
Page 10: ...www fanox com Rev 06 10 226 2 3 Cut out pattern...
Page 12: ...www fanox com Rev 06 12 226 Digital connections Only as an example...
Page 13: ...www fanox com Rev 06 13 226 2 5 Terminals...
Page 49: ...www fanox com Rev 06 49 226...
Page 50: ...www fanox com Rev 06 50 226...
Page 51: ...www fanox com Rev 06 51 226...
Page 52: ...www fanox com Rev 06 52 226...
Page 200: ...www fanox com Rev 06 200 226...
Page 225: ...www fanox com Rev 06 225 226 NOTES...
Page 226: ...www fanox com Rev 06 226 226...