4.15. IEC 60255-151 Curves
The IEC curves follow the following mathematical equation:
K
D
B
Q
V
D
A
t
P
Where:
adjusted
I
I
V
And we have the following curves:
•
Inverse Curve
•
Very Inverse Curve
•
Extremely Inverse Curve
•
Long time inverse
Which relate to the parameters figuring in the following table:
Parameters
A
P
Q
B
K
Long Time Inverse
120
1
1
0
0
Ext. Inverse
80
2
1
0
0
Very Inverse
13,5
1
1
0
0
Inverse
0,14
0,02
1
0
0
The curve can mode from its axis using the D time selection device, which the user can adjust.
I
adjusted
is the initial operating current, set by the user.