5.8.
Configurable Inputs
The SIL-D has 6 digital inputs that can be set by the user. These inputs can be configured
from the HMI, or by using the SICom program.
The inputs are configured by associating the logical inputs with the physical input that they
require, or else no association is made if that logical input is not in use. Therefore, a single
physical input can be associated with more than one logical input.
The default input configuration is shown below:
Logic
In1
In2
In3
In4
In5
In6
Not configured
52 a
52 b
X
External trip
50P block
Reverse directionality
Fault init
79 Pickup
79 Permission
Level 79 Lock
Pulse 79 Lock
Pulse 79 unlock
50BF Pickup
Table 1
Table 2
Reset
Continuity A
Continuity B
Logical signal 1
Logical signal 2