background image

9

INTERIOR DUCTING INSTALLATION

•  To maximize airflow through the ductwork system, all ducts should be kept short and have as few bends or elbows as possible.
•  45º elbows are preferable to 90º.
•  Use “Y“ ducts instead of “T” ducts whenever possible.
•  All duct joints must be fastened with screws or duct sealant and wrapped with aluminum foil duct tape to prevent leakage.
•  Galvanized ducting from the FAA to the living areas in the house is recommended whenever possible, although flexible ducting 

can be used in moderation when necessary.

•  To avoid possible noise transfer through the ductwork system, a short length (approximately 300 mm, 12’’) of nonmetallic flexible 

insulated duct should be connected between the FAA and the supply/exhaust ductwork system.

•  The main supply and return line to/from the FAA must have the same diameter as the duct connection or larger.
•  Branch lines to the individual rooms may be as small as 100 mm (4’’).

Installing ducting to FAA  

Warning: Always fix and secure the 6" collars with the screws supplied. Avoiding this critical step the unit will accumulate condensation.

Tip to Installer: 

To ensure a better installation and to avoid an undesired bend in the duct, align the duct with the collar before securing over the four 

hooks.

The fresh air from outside and the Exhaust air to outside from the termination ducts to the FAA must be fully insulated of thermal insulation ducts to 
minimize heat loss and gain. All tapes, mastics, and nonmetallic clamps used for field installation of flexible ducts shall be listed and labeled to Standard 
UL 181B - Closure Systems for Use With Flexible Air Ducts and Air Connectors.

Air Connector 

A category of flexible duct not meeting the requirements of an Air Duct per UL 181 Standard (not tested for flame penetration, puncture 

and impact) and having limitations on use, length and location as defined by NFPA 90A and 90B. Air Connectors are identified by a “round shape” listing 
label of the listing agency.

Air Duct 

A category of flexible duct tested and classified as to the Surface Burning Characteristics in accordance with the UL 181 Standard. Air Ducts 

are identified by a “rectangular shape” listing label of the listing agency.

To ensure quiet operation of ENERGY STAR qualified FAA, each product should be installed using sound attenuation techniques appropriate for the 
installation. Once insulated flex is attached to the collar, slide collar in keeper section, fixed collar to the unit with four screws supplied in installation 
kit to insure a proper seal.

 

 

 Warning

: To reduce air leakage in the final installation always seal the joint between all collars and keepers with aluminum tape or mastic.

Supply air grilles location

In homes without a forced air furnace, fresh air should be supplied to all habitable rooms, including bedrooms and living areas. It should be supplied 
from high wall or ceiling locations. Grilles that diffuse the air comfortably are recommended. In homes with a forced air furnace, you may want to connect 
the FAA to the furnace ductwork (see information below).

Exhaust air grilles location

The stale air exhaust system is used to draw air from the points in the house where the worst air quality problems occur. It is recommended that return 
air ducts be installed in the bathroom, kitchen, and laundry room. Additional return air ducts from strategic locations may be installed. The furnace 
return duct may also be used to exhaust from. In this method, the exhaust air is not ducted back from bathrooms, kitchens, etc to the HRV with 
“dedicated lines”.

Insert vinyl duct over the hooks 

and seal with a Tie wrap

Insert insulation inside the double 

collar.

Finish by taping the vapor 

barrier to the collar to insure 

proper seal.

Slide collar on the unit.

Fix and secure with four screws supplied 

and seal all joints.

As per building codes and installation requirements for combustion appliances:

Air return ducts, or openings for air return, should not be placed in enclosed spaces containing combustion 

appliances that are subject to spillage.

Summary of Contents for ATMO Series

Page 1: ...signs components and specifications to maintain their technological leadership position Please visit our website www fantech net for more detailed technical information Fantech se r serve le droit de...

Page 2: ...pment i e Gas Furnaces Oil Furnaces Wood Stoves etc Products are designed and manufactured to provide reliable performance but they are not guaranteed to be 100 free of defects Even reliable products...

Page 3: ...XTERIOR DUCTING INSTALLATION Weatherhood Location 8 Installing the ducting to the weatherhood 8 INTERIOR DUCTING INSTALLATION General Tips 9 Installing duct to FAA 9 Supply Exhaust Air Grilles Locatio...

Page 4: ...53 25 60 28 501 1000 47 93 45 21 53 24 60 28 68 31 75 35 1001 1500 94 139 60 28 68 31 75 35 83 38 90 42 1501 2000 140 186 75 35 83 38 90 42 98 45 105 49 2001 2500 187 232 90 42 98 45 105 49 113 52 120...

Page 5: ...YSTEM BEST FOR NEW CONSTRUCTION 1 Stale air is drawn from key areas of the home requiring local exhaust bathroom kitchen laundry room 2 Fresh air is distributed directly to habitable rooms in the hous...

Page 6: ...ing for Partially Dedicated System Air from inside Unit air flow should be balanced while FAA is on Normal speed and furnace blower is running Air return Cold air return Ductwork layout may dif fer de...

Page 7: ...ould be balanced while FAA is on Normal speed and furnace blower is running 1 m 3 3 min recommended Cold air return Ductwork layout may dif fer depending on model FAA Furnace ducting for Simplified In...

Page 8: ...rrier must be completely sealed to the outer wall and the FAA using tape and or caulking A good bead of high quality caulking preferably acoustical sealant will seal the inner flexible duct to both th...

Page 9: ...round shape listing label of the listing agency Air Duct A category of flexible duct tested and classified as to the Surface Burning Characteristics in accordance with the UL 181 Standard Air Ducts a...

Page 10: ...top Stovetop fan Central vacuum system Bathroom exhaust fans unless they are specifically designed for this purpose These appliances may cause lint dust or grease to collect in the FAA damaging the un...

Page 11: ...e FAA The drain nipple is placed upside down in the unit to prevent it being damaged during shipping or the installation of the unit The Switch on the electrical box is used to toggle between STANDBY...

Page 12: ...hed press on next and move on to the next stage STAGE 2 BALANCE SUPPLY FAN ONLY IN HIGH SPEED In this step balance supply fan and measure airflow on the supply air side Pressing on up or down will adj...

Page 13: ...mizing energy use associated with ventilation Set preferred indoor relative humidity range and ventilation mode for day and night conditions No battery to replace all programmed settings are retained...

Page 14: ...stem Use in bathroom kitchen laundry room WALL CONTROLS CONT D MDEH SERIES FEATURES CONNECT TO MDEH1 Rotary dial Dehumidistat Multiple units can be used We recommend setting the relative humidity abov...

Page 15: ...15 Fantech ON Model ON ON ON ON LOW SPEEDS 90V 75V J4 J5 J6 WIRING DIAGRAM ATMO PRODUCT LINE Observe polarity on all accessory controls where applicable...

Page 16: ...TION TO A COOLING SYSTEM On some newer furnaces and older thermostats energizing the R and G terminal at the furnace has the effect of energizing the Y at the thermostat and thereby turning on the coo...

Page 17: ...power supply at site Have electrician check supply voltage Ductwork is restricting airflow Check duct installation Improper speed control setting Increase the speed of the FAA i e change unit control...

Page 18: ...al damages incurred in the use of the ventilation system Fantech is not responsible for providing an authorized service centre near the purchaser or in the general area Fantech reserves the right to s...

Page 19: ...moment et sans pr avis les caract ristiques la conception les composants et les sp cifications de ses produits afin de conserver sa position de leader de technologie S il vous pla t visitez notre sit...

Page 20: ...z fournaise mazout po le bois etc Les produits sont con us et fabriqu s pour fournir une performance fiable mais ils ne sont pas garantis 100 sans d faut M me les produits ont des pannes occasionnelle...

Page 21: ...mplacement des hottes 26 Installation de l ensemble des conduits avec hottes 26 INSTALLATION DES CONDUITS INT RIEURS Conseils pratiques 27 Installation des conduits sur le AAF 27 Emplacement des grill...

Page 22: ...n L s Pi3 min L s 500 47 30 128 38 18 45 21 53 25 60 28 501 1000 47 93 45 21 53 24 60 28 68 31 75 35 1001 1500 94 139 60 28 68 31 75 35 83 38 90 42 1501 2000 140 186 75 35 83 38 90 42 98 45 105 49 200...

Page 23: ...nte selon le mod le SYST ME ENTI REMENT SP CIALIS NOUVELLE CONSTRUCTION Installation sugg r e pour Plinthe eau chaude Plancher chauffant Plinthe lectriques Thermopompe mural bibloc Avantages Fourni la...

Page 24: ...Fournaise centrale unit de traitement d air air climatis central Lorsque l installation des endroits habitable n est pas possible ou pratique dispendieux ou lorsque l unit de traitement d air fonctio...

Page 25: ...vici vacu l ext rieur Air frais provenant de l ext rieur L appareil est quilibr vitesse normale et pendant que le ventilateur de la fournaise est en marche Les papareil air frais AAF de Fantech qui ut...

Page 26: ...mur ext rieur et le AAF l aide de ruban ou de produit de calfeutrage D posez un cordon de produit de calfeutrage de premi re qualit du mastic d isolation acoustique de pr f rence pour sceller le cond...

Page 27: ...d UL 181 cat gorie de conduit d air n est pas l preuve de la p n tration de la flamme de la perforation et la r sistance l impact et ayant des limitations sur l utilisation la longueur et la localisat...

Page 28: ...teur de cuisini re Syst me d aspirateur central Ces lectrom nagers peuvent entra ner l accumulation de charpie de poussi re ou de graisse dans le AAF et l endommager MONTAGE CHAINES Assurez vous d avo...

Page 29: ...au de drain Former un siphon avec le conduit pour viter que les odeurs ne remontent dans le syst me Mauvaises odeurs peu probables l int rieur du cabinet car l appareil fonctionnera en pression positi...

Page 30: ...d air frais BAS BAS BAS BAS BAS BAS HAUT HAUT HAUT HAUT HAUT HAUT AUTO MANUAL OPTIONS AUTO MANUAL OPTIONS NEXT AUTO MANUAL OPTIONS NEXT 0 ADJUST AUTO MANUAL OPTIONS NEXT 0 BALANCE TAPE 1 R GLER LE NIV...

Page 31: ...la ventilation R glage de la plage d humidit int rieure relative et du mode de ventilation favoris pour le jour et la nuit Aucune pile remplacer tous les r glages programm s sont conserv s en cas de p...

Page 32: ...OLS CONT D S RIE MDEH CARACT RISTIQUES RELIER MDEH1 D shumidistat molette Plusieurs commandes peuvent tre utilis es Nous recommandons de fixer le taux d humidit relative au del de 80 l t D D S RIE EDF...

Page 33: ...33 Fantech ON Model ON ON ON ON LOW SPEEDS 90V 75V J4 J5 J6 Respectez la polarit sur tous les acces soires de contr les Le cas ch ant SCH MAS LECTRONIQUES...

Page 34: ...ion de la borne Y du thermostat et cons quemment la mise sous tension du syst me de refroidissement Si votre syst me est muni d un tel type de thermostat vous devez respecter le c blage de verrouillag...

Page 35: ...cacit du AAF V rifiez le r seau de conduits Mauvais r glage de la commande de vitesse Augmentez la vitesse du AAF i e changez la vitesse de l appareil de vitesse R DUITE vitesse NORMALE avec le contr...

Page 36: ...nu de respecter tous les codes en vigueur dans sa r gion Les pi ces y compris les pi ces de rechange pos es ult rieurement sont garanties pendant 5 ans partir de la date d achat de l appareil Les mote...

Page 37: ...be 461102 Kit Chain 404261 Kit Wall Bracket 463942 Wiring Diagram 463927 11 Installation Manual 463913 Filter MERV 8 Pack of 2 463943 Filter MERV 13 Pack of 2 463944 Kit AUX 24V Damper 463947 ATMO 200...

Page 38: ...38 NOTE...

Page 39: ...39 NOTE...

Page 40: ...make technical changes For updated documentation please refer to www fantech net Fantech Fantech se r serve le droit de faire des changements tech niques Pour de la documentation jour s il vous pla t...

Reviews: