Wiring Procedure

Please Note: The fan motor, capacitor and pressure switch connec-
tions are pre-wired from the factory. 

Step 1.

Remove the screws securing the terminal box cover plate located on
the side of the fan. All fan motor connections are prewired to an elec-

trical terminal strip. A 

³|₈

" romex type cable restraint connector will

be needed to secure the wiring through the knockout provided on the
side of the terminal box. 

Step 2.

Bring incoming electrical service through the romex connector and
the fan knockout. Be sure to place the connector nut over the wiring
coming into the terminal box. There are three open ports on the ter-
minal strip. Using a small regular screwdriver, tighten the Neutral
(White) wire of the incoming supply under the open terminal labeled
"N". Tighten the Line (Black) wire of the incoming supply under the
open terminal labeled "L". Tighten the Ground (Green) wire of the
incoming supply under the open terminal marked "     ". For reference,
a wiring diagram is included on the inside of the terminal box lid.

Step 3.

Secure the romex connector. Secure the incoming supply with the
romex connector. Replace the fan terminal box cover.

N

L

Illustration 5

DBF110 Wiring – Fan and Pressure Switch

Warranty and Maintenance

Important Notice: Prior to performing Steps 1 - 4, be certain that the
electrical supply to the fan/switch is turned off.

If fan fails to start when the dryer cycle begins, please follow the pro-
cedure listed below:

1. Check the incoming supply for proper voltage.

2. Consult schematic shown above (also included on inside of fan

wiring terminal lid) to ensure proper connection.

3. If possible, use a meter to test for continuity across the fan

motor leads. In order to do this, the capacitor and pressure
switch must be disconnected (do not test the capacitor - it will
not meter continuity). If motor leads show continuity, rewire the
fan, capacitor and pressure switch.

4. Turn on the electrical supply and restart the dryer cycle. Check to

be certain that fan starts.

If fan still fails to start after performing Steps 1 – 4, continue follow-

ing the procedure as listed below: 

5. Verify that the pressure switch diaphragm is vertical as shown in

Illustration 2 of these instructions. If the diaphragm is not verti-
cal, reposition the pressure switch and check for fan operation
against another dryer cycle. 

6. Verify that the tubing is not crimped and that the tubing connec-

tor nipples are not obstructed.

7. If switch diaphragm is vertical and fan still fails to start, with the

electrical supply on: 

a. Remove the tubing from the nipple on the fan and blow

gently into the tubing; 

b. If fan starts, consult Fantech for additional technical sup-

port.

8. If fan fails to start after blowing into the tubing:

a. Disconnect incoming power supply at the source.

b. Remove the pressure switch leads from the wiring terminal

block

c. Connect the incoming power supply directly to the fan

motor as shown in "FR110 Wiring" diagram below.

d. Turn on power to fan.

9. If fan fails to start, please consult Fantech for additional techni-

cal support.

Recommended Maintenance

1. Since fan bearings are sealed and provided with an internal lubri-

cating material, no additional lubrication is necessary.

2. Fan impeller may accumulate lint. Periodic inspection, based upon

dryer usage, should be performed to ensure that the fan impeller
is not obstructed or loaded with lint. Under normal conditions, fan

should be inspected a minimum of every Six (6) Months. Note:
Excessive booster fan noise or vibration may be an indication of
lint buildup on the impeller. To inspect and clean the impeller:

a. Disconnect the incoming power supply at the source.

b. Remove the duct from the fan inlet and remove any lint

buildup on the impeller.

c. Reconnect the duct to the fan. Turn power supply on.

Troubleshooting

Blue

Brown

Power

to Fan

Red

White

Black

Green

Terminal block in

fan wiring box

Neutral

115V Line (Supply)  Electrical supply, 115V

Ground

Capacitor

Motor

Leads

Brown (Z2)

Blue (U2)

Black (TK)

Capacitor

Neutral side of

115V supply

Line side of

115V supply

Fan Only Wiring 

(Reference for Troubleshooting Step 8c)

Black

Summary of Contents for DBF110

Page 1: ...TER SYSTEM INSTALLATION INSTRUCTIONS DISPOSITIF DBF110 D AMPLIFICATION DU SYSTÈME DE VENTILATION DES SÉCHOIRS À LINGE INSTRUCTIONS D INSTALLATION SISTEMA DE REFUERZO DE ESCAPE DE LA SECADORA DBF110 INSTRUCCIONES DE INSTALACION ...

Page 2: ...nned duct run measure from the dryer to external venting point in roof or wall For each bend or elbow add 5 7 feet to your total duct run calculations The DBF4XL can be used on runs up to 108 feet Pressure Sensor Switch Operation Fantech s DBF110 is equipped with Fantech s Patented DB10 pressure switch The DB10 is a positive pressure sensing switch which recognizes dryer operation and activates th...

Page 3: ... SERVICE TO THE FAN IS LOCKED IN OFF POSI TION 1 This unit has rotating parts and safety precautions should be exer cised during installation operation and maintenance 2 CAUTION For General Ventilation Use Only Do Not Use To Exhaust Hazardous Or Explosive Materials And Vapors 3 WARNING TO REDUCE THE RISK OF FIRE ELECTRIC SHOCK OR INJURY TO PERSONS OBSERVE THE FOLLOWING a Use this unit only in the ...

Page 4: ... cycle Check to be certain that fan starts If fan still fails to start after performing Steps 1 4 continue follow ing the procedure as listed below 5 Verify that the pressure switch diaphragm is vertical as shown in Illustration 2 of these instructions If the diaphragm is not verti cal reposition the pressure switch and check for fan operation against another dryer cycle 6 Verify that the tubing i...

Page 5: ...sitive qui identifie le fonctionnement du séchoir et active le ventilateur d amplification à partir d un circuit électrique indépendant Cela élimine non seulement les connexions tran sitant par les circuits du séchoir ce qui peut en annuler la garantie mais aussi l installation de systèmes manuels nécessitant l attention d un opérateur ou celle de coûteux systèmes de détection électrique ou thermi...

Page 6: ...e de fabrica tion b Avant tout entretien ou nettoyage coupez le courant au tableau électrique et verrouillez ce dernier pour empêcher l activation acci dentelle du ventilateur Quand le système de coupure de courant ne peut pas être verrouillé attachez solidement sur le tableau élec trique un dispositif de signalisation bien en vue tel qu une éti quette c Les travaux d installation et de branchemen...

Page 7: ...uité n y sera mesurée Si les fils d amenée indiquent une continuité recâblez le ventilateur le capaciteur et le rupteur de pression 4 Rebranchez l alimentation électrique et redémarrez le cycle du séchoir Vérifiez que le ventilateur démarre Si le ventilateur ne démarre toujours pas après que vous êtes passés par les étapes 1 4 continuez la procédure telle qu indiqué ci dessous 5 Vérifiez que le di...

Page 8: ...nex ión de la secadora y el conducto de escape se deben estirar para que queden lo más lisas posible Operación del Interruptor Sensor de Presión El DBF110 de Fantech está equipado con un interruptor de presión DB10 paten tado por FanTech El DB10 de Fantech es un interruptor sensor de presión posi tiva que capta la operación de la secadora y activa el ventilador de refuerzo medi ante un circuito el...

Page 9: ...OR QUEDE ASEGURADA EN LA POSICION OFF DESCONECTADA 1 Debido a que esta unidad tiene piezas rotatorias se deben tomar precau ciones de seguridad durante su instalación operación y mantenimiento 2 PRECAUCION Sólo para ventilación en general No Utilizar como Extractor de Materiales Peligrosos o Explosivos ni Vapores 3 Advertencia Para reducir el riesgo de incendio conmocion electrica o lesiones perso...

Page 10: ... contactos del motor del ventilador Para esto hay que desconectar el capac itor y el interruptor de presión No compruebe el capacitor ya que el mismo no da continuidad Si los contactos del motor tienen continuidad vuelva a conectar el ventilador el capacitor y el interruptor de presión 4 Conecte la alimentación eléctrica y reactive el ciclo de la secadora Compruebe la activación del ventilador Si ...

Page 11: ...ts spécifiques reconnus par la loi et sont régies par les lois sur la protection du consommateur appro priées Il est possible que différents états offrent d autres droits Garantía por cinco 5 años DURANTE EL PERÍODO INTEGRO DE LA GARANTÍA FANTECH reparará o reemplazará toda parte que presente un defecto en el material o en la mano de obra Es posible que el producto deba ser devuelto a la fabrica F...

Page 12: ... AND VERIFICATION OF ACTUAL DEFECT BY FANTECH THE FOLLOWING WARRANTIES DO NOT APPLY Damages from shipping either concealed or visible Claim must be filed with freight company Damages resulting from improper wiring or installation Damages or failure caused by acts of Gad or resulting from improper con sumer procedures such as 1 Improper maintenance 2 Misuse abuse abnormal use or accident and 3 Inco...

Reviews: