Start Up 

On power up or if a reset command from the MLM application is being executed, 

the display will initially indicate the WS firmware revision number, with the function 

characters indicating 

Ur

. The display shown here indicates version 2.05. After a few 

seconds the display will revert to the default temperature display and the diffuser 

will enter the initialization mode. 

 

Initialising  

The top and bottom end-stop bars will flash to indicate the diffuser is in initialization 

mode. During this phase, the diffuser is being driven to the maximum open position 

to reference the actuator position. The down arrow will display to indicate 

movement towards the open end-stop. Once the maximum open position has been 

reached, the diffuser will enter control mode. If at this point the diffuser zone 

grouping has been commissioned, the diffuser will enter the heating or cooling 

modes of operation. If the diffuser zone grouping has not been set up, with the 

default zone number still set to zero, the diffuser(s) will remain static in this initialize 

state. Note: Should the up and down arrows flash simultaneously, it indicates the 

actuator motor is in the over-current condition. 

 

Temperature Display 

The default display shows room temperature. The top left function display shows the  

temperature source: 

 

Control temperature not selected – the display shows the space temperature measured 

by the wall-stat. No temperature is selected for control purposes.  

 

Onboard Control temperature – the display shows onboard temperature, as measured 

inside the diffuser. This temperature is used for the room temperature control.  

 

Remote Control temperature – the display shows temperature, as measured by the 

wall-stat. This temperature is used for the room temperature control. 

 

Set point Selection 

Set point selection is achieved by pressing either the up or down arrow button 

momentarily. The buzzer will sound once, the 

SP 

icon will switch on and the current 

set point value will show on the digital display. The default value is 22°C (71°F). The 

top left function digits will indicate respectively the source of the set point and 

which set point is active. If the function display shows 

r1

, it indicates the ‘remote 

set point’ (wall-stat) is the temperature source and set point 1, i.e. ‘normal control’ 

is currently active. Should the function digits show 

o2 

it indicates an onboard-

master controller (inside the diffuser) is where the set point is activated and the 

back-off set point is active at the current time. By pressing the up or down buttons 

the set point value will increment or decrement in 0.5 degree intervals. Please note only  

set point 1, for normal control can be edited by this function. Pressing the enter  

button (right bottom) will exit the set point function. 

 