background image

Part No

.:  INST-RICKWS

  

 08/12 

Page 

4

 of 

5

 

Step Through Menu 

The user has the option to step through the diagnostic and manual control menu. Pressing the right 

top button (Function Select) for 5 seconds will activate this feature. The buzzer will sound once and 

the display will advance to the next function. To exit this mode, the user must press the Function 

Select button for 5 seconds before the buzzer will sound and the display will revert to the (default) 

space temperature value. The Step Through Menu will select the following functions: 

 

 

Menu 1 - Change-over display 

The top left function digits displays 

CO 

to indicate the supply air (changeover) 

temperature is being displayed. If no supply air sensor is connected the display 

will indicate zero. Press the Function Select button to advance to the next display. 

 

 

 

 

Menu 2 - Remote temperature display 

The top left function displays 

to indicate the remote (wall-stat) temperature is 

being displayed. This temperature is displayed regardless of temperature selection 

for control purposes. Press the Function Select button to advance to the next 

display. 

 

 

Menu 3 - Real time clock function 

The watch icon will switch on to indicate the RTC function is selected. The current 

time, hh:mm will show. The top left function displays 

dx

, with 

being any digit 

between 1 and 7 to indicate the current day of the week. Monday is displayed as 

day 1. To edit the RTC, press the enter button and the minute display will flash. 

Select the current minute value with the up or down buttons. Press enter again 

and select the current hour. Enter again and select the current day. Pressing enter 

again will now exit the RTC edit function. The RTC facilitates the back-off control 

 function for energy conservation. The back-off function is activated through the 

MLM Application by setting the SP2 value during commissioning. Press the 

Function Select button to exit this function and advance to the next display. 

 

Further Information 

As previously mentioned further menu functions are available if activated using the MLM software. 

If these appear please refer to the Extended Rickard Wall Stat Manual for further information. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 