background image

15

Troubleshooting

Problem

Causes

Solutions

Air is too dry

Insufficient water vapour generated

Install humidifier

Air is too humid

Sudden increase in humidity by cooking or bathing

Ventilate at the source of the problem using a HRV or additional fan

Sudden change in temperature

Wait until outside temperature stabilizes (winter). Heating will also improve
situation.

Storing too much wood for heating

Store a majority of your wood outside. Even dried, a cord of wood contains 
more than 20 gallons of water.

Dryer vent exhaust is inside home

Arrange outside vent for dryer.

Poor air circulation near windows

Open curtains or blinds. Bay or bow windows may require mechanical method.

HRV not operating (during winter)

Check power to the unit

Persistent condensation
on window

Poor air circulation near windows

Open curtains or blinds. Bay or bow windows may require mechanical method.

Poor Air Flows

1/4" (6mm) mesh on the outside hoods is plugged

Clean exterior hoods or vents

Filters plugged

Remove and clean filter

Core obstructed

Remove and clean core

Indoor grilles closed or blocked

Check and open grilles

Dampers are closed (if installed)

Have electrician check supply voltage

Poor power supply at site

Check duct installation

Ductwork is restricting HRV/ERV

Supply air feels cold

Poor location of supply grilles, the airflow may irritate 
the occupant

Locate the grilles high on the walls or under the baseboards, install ceiling 
mounted diffuser or grilles so as not to directly spill the supply air on the oc-
cupant (eg. Over a sofa)
Use superior grilles such as Fantech CG grille A small duct heater (1kw) 
could be used to temper the supply air
Placement of furniture or closed doors is restricting the movement of air in 
the home

Outdoor temperature extremely cold

If supply air is ducted into furnace return, the furnace fan may need to run 
continuously to distribute ventilation air comfortably

HRV / ERV and / or Ducts Frosting 

up

HRV/ERV air flows are improperly balanced

Have HVAC contractor balance the HRV/ERV airflows

Malfunction of the HRV defrost system

Note: minimal frost build-up is expected on cores before unit initiates defrost 
cycle functions

Outdoor temp. extremely cold

Install duct heater

Condensation or Ice Build Up in 
Insulated Duct to the Outside

Incomplete vapour barrier around insulated duct

Tape and seal all joints

A hole or tear in outer duct covering

Tape any holes or tears made in the outer duct covering 
Ensure that the vapour barrier is completely sealed.

Condensation or Ice Build Up in 
Insulated Duct to the Outside

Incomplete vapour barrier around
insulated duct

A hole or tear in outer duct covering

Tape and seal all joints

Tape any holes or tears made in the outer duct covering

Ensure that the vapour barrier is completely sealed.

Summary of Contents for SH704

Page 1: ...of the National Building Code and or ASHRAE s Good Engineering Practices Fantech reserves the right to modify at any time and without notice any or all of its products features designs components and...

Page 2: ...n equipment i e Gas Furnaces Oil Furnaces Wood Stoves etc Products are designed and manufactured to provide reliable performance but they are not guaranteed to be 100 free of defects Even reliable pro...

Page 3: ...fied installation Option 2 8 EXTERIOR DUCTING INSTALLATION Weatherhood Location 9 Installing the ducting to the weatherhood 9 INSTALLING DUCTS TO FROM INSIDE General Tips 10 Supply Exhaust Air Ducting...

Page 4: ...area Bedrooms 0 1 2 3 4 5 6 7 7 Ft2 m2 CFM L s CFM L s CFM L s CFM L s CFM L s 1500 139 30 14 45 21 60 28 75 35 90 42 1501 3000 139 1 279 45 21 60 28 75 35 90 42 105 50 3001 4500 279 1 418 60 28 75 35...

Page 5: ...eas of the home requiring local exhaust bathroom kitchen laundry room 2 Fresh air is distributed directly to habitable rooms in the house bedrooms living room 3 The HRV s airflow must be balanced afte...

Page 6: ...st operate when ventilation from HRV is required The furnace should be set to run continuously or interlocked with HRV 2 Stale air is drawn from key areas of the home bathroom kitchen laundry room 3 F...

Page 7: ...ection should be upstream of the HRV s supply air connection when ducting to the furnace s cold air return 4 Due to the difference in pressure between the HRV and the equipment it is being connected t...

Page 8: ...and furnace blower is running Outside Fresh air to living areas 1 m 3 3 min recommended Cold air return HRV Furnace ducting for Simplified Installation Option 2 Suggested installation for When bathro...

Page 9: ...liner which acts as a vapor barrier must be completely sealed to the outer wall and the HRV ERV using tape and or caulking A good bead of high quality caulking preferably acoustical sealant will seal...

Page 10: ...ns Grilles that diffuse the air comfortably such as Fantech Contour Grilles are recommended To avoid possible noise transfer through the ductwork system a short length approximately 12 300 mm of nonme...

Page 11: ...ing drain line SH704 VH704 ONLY Drainline not included in kit Through normal operation and during its defrost mode the HRV may produce some condensation This water should flow into a nearby drain or b...

Page 12: ...measuring station s air direction arrow points in the direction of the airflow Secure the flow measuring station with duct tape 2 Before taking the reading make sure that the megnehelic gauge is leve...

Page 13: ...13 Electrical connections SH704 VH704...

Page 14: ...14 SE 704N Electrical connections Cont d...

Page 15: ...ocation of supply grilles the airflow may irritate the occupant Locate the grilles high on the walls or under the baseboards install ceiling mounted diffuser or grilles so as not to directly spill the...

Page 16: ...ortation removal and installation fees are the responsibility of the purchaser The purchaser is responsible to adhering to all codes in effect in his area The warranty is limited to 5 years on parts a...

Page 17: ...Kit 8 x 8 3 405116 3 Heat Recovery Cell 8 5 x 8 5 x 8 404350 4 Wing Screw 10 32 412070 5 Capacitors 2uF 412315 6 PCB 412072 7 Door Switch 410867 8 Kit Drain Plug 40315 Temperature Probe 40286 Door Ass...

Page 18: ...78 2 Electrostatic Filters Kit 8 x 8 3 405116 3 Heat Recovery Cell 9 x 9 x 8 403120 4 Wing Screw 10 32 412070 5 Capacitors 2uF 412315 6 PCB 412072 7 Door Switch 410867 8 Kit Drain Plug 40315 Temperatu...

Page 19: ...ion SE704 40357 1 Motor R2E 133 BH94 18 404378 2 Electrostatic Filters Kit 8 x 8 3 405116 3 Energy Recovery Cell 422731 4 Wing Screw 10 32 412070 5 Capacitors 2uF 412315 7 Door Switch 410867 Kit Wall...

Page 20: ...Fantech reserves the right to make technical changes For updated documentation please refer to www fantech net Fantech...

Reviews: