background image

9

Exterior ducting installation

Weatherhood location

•   Decide where your intake and exhaust hoods will be located.

Locating the Intake Weatherhood

•  Should be located upstream (if there are prevailing winds) from the 

exhaust outlet.

• At a minimum of 2m (6’) away from dryer vents and furnace exhaust 

(medium or high efficiency furnaces), driveways, oil fill pipes, gas meters, 
or garbage containers.

• At a minimum height of 460mm (18’’) above the ground, or above the level 

of expected snow accumulation.

• At a minimum distance of 1m (3’) from the corner of the building.
• Do not locate in the garage, attic, crawl space, or underneath deck.

Locating the Exhaust Weatherhood

•  At least 460mm (18") above ground or above the depth of expected snow accumulation
• At least 1m (3’) away from the corner of the building
• Not near a gas meter, electric meter or a walkway where fog or ice could create a hazard
• Do not locate in a garage, workshop or other unheated space

Installing the ducting to the weatherhoods

A well designed and installed ducting system will allow the HRV/ERV to operate at its maximum 
efficiency. The inner liner of the flexible insulated duct must be secured to the sleeve of the 
weatherhood (as close to the outside as possible) and to the appropriate duct connection on 
the HRV/ERV. The insulation should remain full and not crushed. The outer liner, which acts as 
a vapor barrier, must be completely sealed to the outer wall and the HRV/ERV using tape and/
or caulking. A good bead of high quality caulking (preferably acoustical sealant) will seal the 
inner flexible duct to both the HRV/ERV duct connection and the weatherhood prior to securing 
them.
To minimize airflow restriction, the flexible insulated duct that connects the two outside weatherhoods to the HRV/ERV should be stretched tightly 
and be as short as possible.
Twisting or folding the duct will severely restrict airflow.

See “Installation Diagram Examples” for installation examples.

1

  Using the duct connection of 

the outside hood, outline the 
intake & exhaust holes to be 
cut. The holes should be slightly 
larger than the duct connection 
to allow for the thickness of the 
insulated flexible duct. Cut a 
hole for both the intake and 
exhaust hoods.

Push the hood into the opening 
and then attach the hood to the 
outside wall with mounting 
screws. 
Repeat the installation 
procedure for both the supply 
and exhaust hoods.

2

  Pull the insulated flexible duct 

through the opening until it is 
well extended and straight. 
Slide the duct’s inner vinyl sleeve 
over the hood duct connection 
and secure. Pull the insulation 
over the duct and pull the 
vapour barrier over the sleeve. 
Secure with appropriate tape or 
sealant.

4

  Using a caulking gun, seal 

around both hoods to prevent 
any leaks.

Steps for hood installation

36" (1m)

min.

INTAKE

OUTSIDE CORNER

INSIDE CORNER

EXHAUST

18" (460mm) min.

18" (460mm) min.

6' (2m)

min.

36” (1m)

min.

Summary of Contents for SH704

Page 1: ...of the National Building Code and or ASHRAE s Good Engineering Practices Fantech reserves the right to modify at any time and without notice any or all of its products features designs components and...

Page 2: ...n equipment i e Gas Furnaces Oil Furnaces Wood Stoves etc Products are designed and manufactured to provide reliable performance but they are not guaranteed to be 100 free of defects Even reliable pro...

Page 3: ...fied installation Option 2 8 EXTERIOR DUCTING INSTALLATION Weatherhood Location 9 Installing the ducting to the weatherhood 9 INSTALLING DUCTS TO FROM INSIDE General Tips 10 Supply Exhaust Air Ducting...

Page 4: ...area Bedrooms 0 1 2 3 4 5 6 7 7 Ft2 m2 CFM L s CFM L s CFM L s CFM L s CFM L s 1500 139 30 14 45 21 60 28 75 35 90 42 1501 3000 139 1 279 45 21 60 28 75 35 90 42 105 50 3001 4500 279 1 418 60 28 75 35...

Page 5: ...eas of the home requiring local exhaust bathroom kitchen laundry room 2 Fresh air is distributed directly to habitable rooms in the house bedrooms living room 3 The HRV s airflow must be balanced afte...

Page 6: ...st operate when ventilation from HRV is required The furnace should be set to run continuously or interlocked with HRV 2 Stale air is drawn from key areas of the home bathroom kitchen laundry room 3 F...

Page 7: ...ection should be upstream of the HRV s supply air connection when ducting to the furnace s cold air return 4 Due to the difference in pressure between the HRV and the equipment it is being connected t...

Page 8: ...and furnace blower is running Outside Fresh air to living areas 1 m 3 3 min recommended Cold air return HRV Furnace ducting for Simplified Installation Option 2 Suggested installation for When bathro...

Page 9: ...liner which acts as a vapor barrier must be completely sealed to the outer wall and the HRV ERV using tape and or caulking A good bead of high quality caulking preferably acoustical sealant will seal...

Page 10: ...ns Grilles that diffuse the air comfortably such as Fantech Contour Grilles are recommended To avoid possible noise transfer through the ductwork system a short length approximately 12 300 mm of nonme...

Page 11: ...ing drain line SH704 VH704 ONLY Drainline not included in kit Through normal operation and during its defrost mode the HRV may produce some condensation This water should flow into a nearby drain or b...

Page 12: ...measuring station s air direction arrow points in the direction of the airflow Secure the flow measuring station with duct tape 2 Before taking the reading make sure that the megnehelic gauge is leve...

Page 13: ...13 Electrical connections SH704 VH704...

Page 14: ...14 SE 704N Electrical connections Cont d...

Page 15: ...ocation of supply grilles the airflow may irritate the occupant Locate the grilles high on the walls or under the baseboards install ceiling mounted diffuser or grilles so as not to directly spill the...

Page 16: ...ortation removal and installation fees are the responsibility of the purchaser The purchaser is responsible to adhering to all codes in effect in his area The warranty is limited to 5 years on parts a...

Page 17: ...Kit 8 x 8 3 405116 3 Heat Recovery Cell 8 5 x 8 5 x 8 404350 4 Wing Screw 10 32 412070 5 Capacitors 2uF 412315 6 PCB 412072 7 Door Switch 410867 8 Kit Drain Plug 40315 Temperature Probe 40286 Door Ass...

Page 18: ...78 2 Electrostatic Filters Kit 8 x 8 3 405116 3 Heat Recovery Cell 9 x 9 x 8 403120 4 Wing Screw 10 32 412070 5 Capacitors 2uF 412315 6 PCB 412072 7 Door Switch 410867 8 Kit Drain Plug 40315 Temperatu...

Page 19: ...ion SE704 40357 1 Motor R2E 133 BH94 18 404378 2 Electrostatic Filters Kit 8 x 8 3 405116 3 Energy Recovery Cell 422731 4 Wing Screw 10 32 412070 5 Capacitors 2uF 412315 7 Door Switch 410867 Kit Wall...

Page 20: ...Fantech reserves the right to make technical changes For updated documentation please refer to www fantech net Fantech...

Reviews: