Section II Operation Instructions
II-4
P/N 446613 Issue I Rev. A
Disable Zone/Signals
To disable a zone or signal press and hold the zone/sig disable button and then press
one of the push buttons labeled A-F.
To enable a disabled zone or signal press and hold the zone/sig disable button and then
press the appropriate push buttons for the zone or signal that was disabled.
Indicating Device
Circuit
Button for
Zone/Sig Disable/Enable
1
A
2
B
3
C
4
D
Notification Appliance
Circuit
1
E
2
F
When you disable a zone or signal, the disabled LED turns on steady. In addition the
associated zone or signal trouble LED’s blink.
Quick Test Procedures
A quick test enables you to check the operation of each of the detectors or devices that
make up your system.
A Quick Test enables you to check full system operation. To prepare for the quick test:
!
buttons simultaneously. The Disabled LED will flash indicating Quick Test is
enabled.
To perform the quick test:
1. Activate a zone. The panel should indicate the appropriate way (the Alarm Verify
feature is disabled during Quick Test).
2. The panel indicates for approximately 10 seconds, then resets just as if you had
pressed the System Reset button.
If you leave the panel in quick test mode for more than an hour, the panel will end the
Quick Test and return to normal operation.
The NACs may be disabled for silent operation during Quick Test.