13400 Owner’s Manual
P/N 446613 Issue I Rev. A
II-5
13400 Switches
The following table describes the operation of the panel’s switches.
Note: All the panel’s push-button switches are accessed on the back of the panel door.
Push-button Switch
If you press the button:
System Reset
Panel inactive for 12 seconds with the System Trouble LED flashing.
Panel operational.
Trouble Silence
System Trouble LED on continuous (if from flashing state), while the
trouble or supervisory exists.
Zones that currently have a flashing trouble LED (with the exception of a
supervisory alarm) will be turned continuous on. Troubles and
supervisories that have cleared, their zone LEDs will be turned off.
Panel buzzer will go from slowly pulsating to off.
Alarm Silence
System Alarm LED will be turned continuous on from the flashing state.
Zones currently in alarm will have their alarm lights turned on steady
from a flashing state.
Panel buzzer will go from rapidly pulsating to off.
History Recall
The last Zone Alarm LED will light
The last Zone Trouble LED will light, if the last zone trouble was a
supervisory condition the System Supervisory LED will also light. All
other zone LEDs will extinguish while holding the History Recall button.
The LEDs will be restored when the switch is released.
General Alarm
Signal Circuit relays and Alarm relay activates.
System Alarm LED and Panel buzzer activate.
Zone/Sig Disable
Disabled LED lights.
Associated Zone(s) Trouble LEDs and Signal Trouble LEDs flash.
Trouble relay energizes.
City Tie Disable
Trouble is reported, but Alarm is disabled.
Lamp Test
If the system is in a normal operating condition, then and only then:
All LEDs light, except for the NAC active LEDs.
The LEDs will be restored to their previous state when the switch is
released.