13400 Owner’s Manual
P/N 446613 Issue I Rev. A
I-1
Section I : Descriptions
This section provides an overview of the 13400, including the following:
!
Introduction
!
Minimum control unit configuration
!
Optional control unit configurations
!
Optional
Devices
!
General operating parameters
!
General
Specifications
Introduction
The 13400 is a conventional, modular fire alarm control unit with the following standard
features and options:
Control Unit Features
!
4 Class B (Style B) Initiating Device Circuits (IDC).
!
2 Class B (Style Y) Notification Appliance Circuits (NAC).
!
2.25 amps of Notification Appliance Power.
!
200ma of resettable and/or non-resettable power.
!
.5 amps unfiltered Auxiliary Power (subtracted from NAC Power)
!
General alarm operation.
!
Dry contact status relay outputs, form-C, rated 2.0A at 30VDC / 0.5A at 30 VAC,
resistive, (alarm and trouble).
!
Operates one supervised remote LED annunciator.
!
Battery charger with no and low battery supervision.
!
Push button switches for: system reset, trouble silence, alarm silence, lamp test,
city tie disable, zone/sig disable, general alarm, and history recall.
!
Ground fault detection, positive and negative.
!
Dual level IDC operation for waterflow (zone 4 only) and supervisory devices.
!
Automatic NAC short circuit disconnect circuitry.
Settings for
!
Alarm verification selectable for each IDC.
!
Manual alarm silence with 0, or 1 minute inhibit.
!
Steady output pattern selectable by NAC to be silenceable or non-silenceable.
!
“Quick Test” by system.
!
Silent or audible “Quick Test”.
Expansions and Options
!
Alarm Relay Board providing a form “C”, 2.0 A at 30 VDC or 0.5 A at 30 VAC,
resistive, fire alarm contact from each initiating device circuit and additional alarm
and trouble contacts.
!
Semi-flush mounting trim ring.
!
Remote LED Annunciator Driver with zone alarm outputs.
!
City Tie with Local Energy/Remote Station connections