18
Operation, Installation, and Maintenance Manual
LW-401
5. Press the Drill key to map the selected
Zone to the desired Output.
6. Press the Silence key to select another
Zone to be programmed and return to
Step 3.
7. Press the ACK key when done.
Program Level 6 - Set System Timing
1. Press the Reset key 6 times to select
Program Level 6.
2. Press the Silence key to select one of
the four timing functions to be
programmed as indicated in the following
table:
Example: 6-1 programs the Alarm
Verification Retard/Reset Timer.
Level
Feature
6-1
Verification Retard/Reset Timer
6-2
NAC Inhibit Timer
6-3
NAC Cutoff Timer
6-4
Simplified Zone Code Rounds
Level 6-1 - Set Verification Retard/Reset
Timer
1. The selected Retard/Reset Time is
shown by the red zone LEDs accord-
ing to the following table:
Zone 1 LED
=
15 seconds
Zone 2 LED
=
20 seconds
Zone 3 LED
=
25 seconds
Zone 4 LED
=
30 seconds
Zone 5 LED
=
40 seconds
Zone 6 LED
=
50 seconds
Zone 7 LED
=
50 seconds
Zone 8 LED
=
50 seconds
2. Press the Reset key to advance the
pointer (yellow zone LED) to the
desired time.
3. Press the Drill key to activate the
desired time.
4. Press the ACK key when done.
Level 6-2 - Set NAC Inhibit Timer
1. The selected Inhibit Time is shown by the
red zone LEDs as indicated in the
following table:
Zone 1 LED
=
0 minutes
Zone 2 LED
=
6 seconds
Zone 3 LED
=
30 seconds
Zone 4 LED
=
1 minutes
Zone 5 LED
=
90 seconds
Zone 6 LED
=
2 minutes
Zone 7 LED
=
3 minutes
Zone 8 LED
=
5 minutes
2. Press the Reset key to advance the
pointer (yellow zone LED) to the desired
time.
3. Press the Drill key to activate the desired
time.
4. Press the ACK key when done.
Level 6-3 - Set NAC Cutoff Timer
1. The selected Cutoff Time is shown by the
red zone LEDs as indicated in the
following table:
Zone 1 LED
=
No Cutoff
Zone 2 LED
=
1 minutes
Zone 3 LED
=
2 minutes
Zone 4 LED
=
5 minutes
Zone 5 LED
=
10 minutes
Zone 6 LED
=
15 minutes
Zone 7 LED
=
20 minutes
Zone 8 LED
=
25 minutes
2. Press the Reset key to advance the
pointer (yellow zone LED) to the desired
time.
3. Press the Drill key to activate the desired
time.
4. Press the ACK key when done.