Original notice – User’s manual
16
Only connect suitable electrical receivers to the generator and whose total power
does not exceed the rated power of the generator. The electrical data of the
receivers, such as voltage and frequency, must correspond to those of the
generator. If the receiver information is missing, please ask the manufacturer.
Electrical installations of existing buildings are not permitted.
Never touch exposed cables or disconnected connections.
Never expose the equipment to liquid splashes or weather conditions or place it
on wet ground.
If there is any doubt about the installation, call us.
Choice of connection cables
Observe the sections and lengths recommended in this table when installing the
system or when using extension cords.
SECTION CONSEILLÉE DE CÂBLE
Single-phase
Three-phase
Current intensity
10 A
16 A
32 A
10 A
16 A
Units
mm² AWG mm² AWG mm² AWG mm² AWG mm² AWG
Cable
length
used:
1 to 50 m
4
10
6
9
10
7
1,5
14
2,5
12
51 to 100 m
10
7
10
7
25
3
2,5
12
4
10
101 to 150 m* 10
7
16
5
35
2
4
10
6
9
* This cable length is the maximum length allowed, it must not be exceeded.
Installation method: cables on cable tray or non perforated tablet / permissible
voltage drop: 5% / multiconductor / cable type: PVC 70°C (example: H07RNF) /
ambient temperature: 30°C.