Heat recovery unit with cooling circuit -
RCF
-
0208-6180549-rev. 02
19
GB
Controls manual
Pa A17 Turns compressor OFF if over-tem-
perature
If set to 1 it turns off the compressor if an
over-temperature alarm is generated
Pa A18 Select anti-freeze alarm probe
• 0 = probe AI1
• 1 = probe AI2
Compressor parameters
Pa C01 OFF-ON safety time
The minimum period of time that must elap-
se between turning off the compressor and
turning it on again. It is expressed in tens of
seconds.
Pa C02 ON-ON safety time
The minimum period of time that must elap-
se between turning the compressor on and
turning it on again. It is expressed in tens of
seconds.
Pa C03 Temperature control hysteresis in
Cooling mode
Used to select the activation differential in
Cooling mode.
Pa C04 Temperature control hysteresis in
Heating mode
Used to select the activation differential in
Heating mode.
Pa C05 Regulation step intervention diffe-
rential
Used to set a temperature differential in
relation to the set point beyond which the
second step is activated.
Pa C06 Interval between compressor 1 –
compressor 2 start-up (step)
Used to set a delay between turning on the
first and the second step
Pa C07 Interval between compressor 1 –
compressor 2 shut-down (step)
Used to set a delay between turning off the
first and the second step.
Fan parameters
Pa F01 Fan output configuration
• 0: proportional condensation control TK
output
• 1: ON-OFF TK output
• 2: anti-freeze electric heater output for
water-water machines with gas reversal
• 3: TK ON-OFF output on compressor
Pa F26 Freecooling offset in cooling mode
Moves the freecooling set point in relation to
the cooling set point
Pa F27 Freecooling proportional band in
Cooling mode
Freecooling control band
Pa F28 Freecooling offset in heating mode
Moves the freeheating set point in relation
to the heating set point
Pa F29 Freeheating band in Heating mode
Freeheating control band
Pa F30 Outdoor/internal temperature offset
in freecooling and freeheating
Offset in controller that compares outdoor
and internal temperature
Pa F31 Minimum damper opening
Minimum damper opening value
Pa F32 Freecooling shut-down set point
Outdoor temperature that shuts down free-
cooling
Pa F33 Freecooling shut-down offset
Controller offset that shuts down freecoo-
ling
Evaporator fan parameters
Pa P01 Evaporator fan operating mode
May be used to determine the pump or fan
operating mode
• 0= continuous operation
• 1= fan shuts down as the same time as
the compressor
• 2= continuous operating of fan in cooling
mode, on request in heating mode
• 3= continuous operating of fan in cooling
mode, on request in heating mode
• 4= continuous operating of fan in heating
mode, on request in cooling mode
Pa P02 Delay between fan ON and com-
pressor ON
It sets a delay between the start up of the
fan and the compressor. It is expressed in
seconds.
Pa P03 Delay between compressor OFF
and fan OFF
It sets a delay between the shutdown of the
unit and the fan. It is expressed in seconds.
Anti-freeze/boiler parameters
Pa r01 Configuration of electric heaters in
Defrost mode
Determines electric heater operation when
the defrost function is activated
• 0=On only when requested by temperatu-
re controller
• 1=Always on in Defrost mode
Pa r02 Configuration of electric heaters
activated in Cooling mode
Determines electric heater operating in
Cooling mode
• 0=Off in Cooling mode
• 1=On in cooling mode (depending on
the anti-freeze electric heater regulation
algorithm)
Pa r03 Configuration of electric heaters
activated in Heating mode
Determines electric heater operating in
Heating mode
• 0=Off in Heating mode
• 1=On in Heating mode (depending on
the anti-freeze electric heaters regulation
algorithm)
Pa r04 Configuration of anti-freeze electric
heater control probe in heating mode
Determines the control probe of the electric
heaters in Heating mode
• 0=Controls on probe AI1
• 1=Controls on probe AI2
Pa r05 Configuration of anti-freeze electric
heater control probe in cooling mode
Determines the control probe of the electric
heaters in Cooling mode
• 0=Controls on probe AI1
• 1=Controls on probe AI2
Pa r06 Configuration of electric heaters in
OFF or stand-by mode
Determines the status of electric heaters
when the unit is in OFF or Stand-by mode
• 0=Always off in OFF or stand-by
• 1=On in OFF or stand-by (depending
on the anti-freeze electric heater control
algorithm)
Pa r07 Anti-freeze electric heater set point
in Heating mode
È il valore di temperatura, in heating, al di
sotto del quale vengono attivate le resisten-
ze antigelo.
Pa r08 Anti-freeze electric heater set point
in Cooling mode
It represents the temperature, in Heating
mode, below which anti-freeze electric hea-
ters are activated.
Pa r09 Maximum set point limit for anti-
freeze electric heaters
Sets the maximum set point for anti-freeze
electric heaters.
Pa r10 Minimum set point limit for anti-
freeze electric heaters
Sets the minimum set point for anti-freeze
electric heaters.
Pa r11 Anti-freeze electric heater hysteresis
Pa r12 Enable heat pump shut-down
• 0= heat pump always on
• 1 =heat pump shut down when outdoor
temperature is too cold
Pa r13 Outdoor temperature set point for
deactivation of heat pump
The temperature below which the heat
pump is turned of.
Pa r14 Differential for deactivation of heat