Author – D. Rehe Feb 2020 

 

On current trip and the controller is disabled and the trip relay energises and latches. 
Current Trip can be rest by opening the ENABLE link or by turning off the mains supply 

For F330 controllers fitted with CC,CCE option

 

7.A Bias(Zero) Adjustment

 

1.  Set GAIN & AUX-V potentiometer(POT) fully anti-clockwise 
2.  Purchase a Current Clamp Meter similar as these Clamp Meters. 

300 Amp True 

RMS Clamp Meter

. Or for additional power quality features you can use this 

1000 

Amp True RMS Clamp Power Meter.

 We reccommend the standard Current 

Clamp for most applications as it comes with a impedance test functions which is 
handy to verify failed SCR's or diodes by measuring Anode to Cathode and Gate 
to Cathode for short circuits or low impedance. 

See our Diode SCR Testing Blog 

for the complete test procedure.

 

Note:

 Bias Adjustment can be adjusted from -20% to +20% 

7.B Minimum Control Input

 

1.  Input the minimum Control Signal. I.e 0V, 4mA, or 10K POT to 0 position. 

depending on the input required. Default is 4mA, for 4-20mA input control. 

2.  Clamp the DC output wire using the current clamp.  
3.  Set the BIAS POT to the centre position. 
4.  Input the minimum control input signal. 
5.  Gradually turn the AUX-V potentiometer clockwise until the output current is 

around 5 Amp then adjust the Bias POT until you get zero current through the 
load.  

8.A Gain Adjustment

 

Apply the maximum control signal 10V, 5V, 20mA, or 10K POT position. 

8.B Maximum Control Input

 

1.  Turn the GAIN Potentiometer(POT) fully clockwise. 
2.  Gradually turn the AUX-V potentiometer clockwise until about 5 Amp more than 

the maximum desired output current is measured. Be careful not to adjust to 
higher over the maximum load or you may cause permanent damage to the SCR 
due to overheating. 

3.  Adjust the GAIN POT until the output current is at the maximum desired level. 
4.  Recheck the output current at maximum and minimum control input and re-adjust 

the Bia and Gain as necessary. 

5.  AUX-V POT controls the output voltage and can be left as a maximum limit or 

adjusted as required taking care not to output overvoltage to the load. 

9. Ramp/Soft Start Adjustment

 

The RAMP potentiometer(POT) sets the step response of the controller for any change 
in the control input signal. Setting Range in the standard controller is between 1 and 20 

Summary of Contents for F330 Series

Page 1: ...20 Fastron Oztherm Power Controller F330 Series Calibration Procedure In this article we discuss the calibration procedure for F330 Series Single Phase Thyristor SCR Controllers PCB F311AO Firing Card...

Page 2: ...er sticker on the PCB with a serial number in the format of YY MM Serial Controller Options Identification There are various options available for this controller which the most common are listed and...

Page 3: ...increase as they approach failure several Amps in the worst cases What this means is there will always be a voltage present even when the enable of the controller is not connected and the controller...

Page 4: ...ot have access to a current clamp you can monitor the load voltage instead and it will also stop increasing like the current In both cases you should wind the GAIN POT back and forth a little unit you...

Page 5: ...it is active Note The PW option Power limit takes the voltage into account when limiting the output however with only the C option Current Limit it only limits by current Th reason is due to some appl...

Page 6: ...lamp the DC output wire using the current clamp 3 Set the BIAS POT to the centre position 4 Input the minimum control input signal 5 Gradually turn the AUX V potentiometer clockwise until the output c...

Page 7: ...over the last 30 years See here for a list of available SP versions To check the response time input a step change to the control input and measure the time taken to reach the desired output 10 MI MV...

Reviews: