Connecting UC2 to CDA units (connecting to CD22
and TD1 units)
To connect the UC2 to CD22 series laser displacement sensors and to TD1 series through-
beam edge sensors, connect through CDA series displacement sensor amplifier units.
<Connection example>
Power is supplied from the
CDA units to the sensors.
0V
0V
+V
+V
0V
+V
0V
+V
0V
+V
0V
+V
Power supply
device
Supply power to the UC2 from the IO-Link master unit. Supply power to the inter-connected
CDA units from the same power supply device as the IO-Link master unit.
CD22 series/TD1 series
(Up to two units can be connected to one CDA series unit.)
CDA
series
UC2
Inter-connection connector
IO-Link master unit
18 to 24 VDC
CAUTION
●
The CDA series power supply must be connected to a power supply that is separate from that for the
UC2 and is the same as that for the IO-Link master unit.
●
Power is supplied to the CD22 series and to the TD1 series from the CDA series. The UC2 can be
inter-connected to CDA series main units and expansion units.
●
When inter-connecting the UC2 to the CDA series, be sure to inter-connect the inter-connection main
unit on the left end. If an inter-connection expansion unit is connected on the left end, the inter-connec-
tion connector will be exposed, damaging the product.
●
Up to eight CDA series units can be interconnected.
The number of output information and receiving
distance information varies depending on the setting. Refer to the index list for details.
●
Ensure that the length of the power cable to the unit and to the CDA series is 20 m or less.
●
The operating temperature of the CDA series expansion unit (CDA-S) and the load current of the control
output are restricted by the connected main unit (CDA-M, CDA-DM2) as below.
<CDA-M+CDA-S>
Operating temperature
−25 to +50°C
Load current of control
output
Up to 100mA per output channel Up to 100mA per output channel (Up
to 2A including self-consumption)
Number of connected units
1 unit (Only CDA-M)
2 to 8 units
<CDA-DM2+CDA-S>
Operating temperature
−25 to +50°C
−20 to +45°C
Load current of control
output
Up to 100mA per output channel
Up to 20mA per output channel
Number of connected units
1 unit (Only CDA-DM2)
2 to 8 units
Connecting UC2 to D3RF/D3WF/D4RF series
Use the inter-connection connectors to connect the UC2 to D3RF/D3WF/D4RF series
fiber amplifiers.
Connecting power supply wires
When three or less fiber amplifiers are inter-connected to the UC2, the fiber amplifiers op-
erate with the power supplied from the inter-connection connector of the UC2. When four
or more fiber amplifiers are inter-connected to the UC2, connect the inter-connection
main unit on the left end to the same power supply as the IO-Link master unit.
<Connection example>
0V
0V
+V
+V
0V
+V
0V
+V
Inter-connection connector
When inter-connecting four or more fiber amplifiers, supply power not only to the UC2 but
also to the fiber amplifier main unit on the left end. Also, supply power to the fiber amplifier
main unit and the IO-Link master unit from the same power supply device.
(max. 16 units)
4 units or more
Up to 3 units
Provide supply voltage
to the main unit.
Supply power from the UC2.
UC2
IO-Link master unit
18 to 24 VDC
Power supply
device
Fiber amplifier inter-connection order
When inter-connecting the UC2 to D3RF/D3WF/D4RF series fiber amplifiers, connect
D4RF, D3WF, and D3RF in this order from the side closer to the UC2.
<Connection example>
Inter-connection connector
UC2
D3RF series
D3WF series
D4RF series
CAUTION
●
When inter-connecting the unit to fiber amplifiers, be sure to connect an inter-connection main unit on
the left end. If an inter-connection expansion unit is connected on the left end, the inter-connection
connector will be exposed, damaging the product.
●
A total of up to 16 D3RF/D3WF/D4RF series fiber amplifiers can be inter-connected. The number of
output information and receiving light level information varies depending on the setting. Refer to the
index list for details.
●
Ensure that the length of the power cable to the unit and to the fiber amplifiers is 20 m or less.
●
When using a cable type fiber amplifier, perform insulation processing to prevent the power supply
wires (brown/blue) from short-circuiting. Short-circuits may lead to device damage. Furthermore, in
the case of connector type units, connect the included black cap to the M8 connector when the con-
nector cable is not connected to prevent the pins from short-circuiting.
●
The operating temperature and the load current of control output are restricted by the number of con-
nected units as below.
D3RF/D3WF series
Number of connected unit
1 to 3 unit(s)
4 to 8 units
9 to 16 units
Operating temperature
−25 to +55°C
−25 to +50°C
−25 to +45°C
Load current of control output
100 mA
50 mA
20 mA
D4RF series
Number of connected unit
1 unit
2 units
3 to 5 units
6 to 16 units
Operating temperature
−25 to +55°C
−25 to +55°C
−25 to +50°C
−25 to +45°C
Max. load cur-
rent per output
1 output setting
100 mA
20 mA
20 mA
20 mA
2 outputs setting
50 mA
10 mA
10 mA
10 mA
Connecting UC2 to a combination of CDA series and
D3RF/D3WF/D4RF series units
When inter-connecting the UC2 to CDA displacement sensor amplifier units and D3RF/
D3WF/D4RF series fiber amplifiers, connect CDA, D4RF, D3WF, and D3RF in this order
from the side closer to the UC2.
(It is possible to connect D4RF, CDA, D3WF, and D3RF in that order as well.)
<Connection example>
18 to 24 VDC
IO-Link master unit
Power supply
device
0V
0V
+V
+V
0V
+V
0V
+V
・
Supply power to the UC2 from the IO-Link master unit. Furthermore, supply power not only to the UC2
but also to the fiber amplifier main unit on the left end.
・
Connect the fiber amplifier main unit and the IO-Link master unit to the same power supply device.
・
For the CDA, use an inter-connection expansion unit.
UC2
D3WF series
CDA series (sensor: CD22/TD1 series)
D3RF series
Supply power to the main
unit on the left end.
0V
+V
Inter-connection connector
D4RF series
CAUTION
●
Supply power to the CDA series and D3RF/D3WF/D4RF series units from the same power supply as
that for the IO-Link master unit.
●
When inter-connecting the UC2 to the CDA series, be sure to inter-connect the inter-connection main
unit on the left end. If an inter-connection expansion unit is connected on the left end, the inter-connec-
tion connector will be exposed, damaging the product.
●
A total of up to 16 D3RF/D3WF/D4RF series and CDA series units can be inter-connected. (One CDA
displacement sensor amplifier unit counts as two sensors.)
The number of output information and distance/receiving light level information varies depending on
the setting. Refer to the index list for details.(D3RF/D3WF/D4RF series is the receiving light level infor-
mation and CDA series is distance information.)
●
Ensure that the length of the power cable to the unit and to the CDA series is 20 m or less.
●
When using a cable type D3RF/D3WF/D4RF series unit, perform insulation processing to prevent the
power supply wires (brown/blue) from short-circuiting. Short-circuits may lead to device damage. Fur-
thermore, in the case of connector type units, connect the included black cap to the M8 connector
when the connector cable is not connected to prevent the pins from short-circuiting.
8. System Configuration Example
(When inter-connecting four or more fiber amplifiers and no other types of units
and when using a displacement sensor amplifier unit, connect power supply
wires to the main unit on the left end.)
NF series
fiber unit
Displacement sensors: CD22 series and
edge sensors: TD1 series
Amplifier connection cable
(+ extension cable)
UC2-IOL
IO-Link gateway
Power supply device
IO-Link master unit
18 to 24 VDC
D3RF series/
D3WF series/
D4RF series
fiber amplifier
M84CN series
connector cable
CDA series
displacement
sensor amplifier
unit
●
The UC2 can be inter-connected to up to a total of 16 sensors. (One CDA displace-
ment sensor amplifier unit counts as two sensors.)
The number of output information and distance/receiving light level information varies depending on
the setting. Refer to the index list for details.(D3RF/D3WF/D4RF series is the receiving light level infor-
mation and CDA series is distance information.
●
The power supply connections of the devices vary depending on the devices that are
connected and on the number of devices that are connected. Check the information
under “
7. Connecting
” and connect the power supplies correctly.
9. Specifications
Model
UC2-IOL
IO-Link com-
munication
specifications
Minimum cycle time
2.2 ms
Baud rate
COM3 (230.4 kbps)
ISDU support
Available
IO-Link revision
1.1
Number of process input
data bytes
32
Number of process output
data bytes
0
IO-Link frame type
F-Sequence Type 2.V
Connected
devices
Connectable models
D3RF/D3WF/D4RF series inter-connection main unit
and expansion unit
CDA series main unit and expansion unit
Number of connectable units
Up to 16 (One CDA unit requires two spaces.)
Connection type
5-pin connector for inter-connection (functions as an
inter-connection end unit)
Indicators
Power indicator (green), SIO: lit at all times, IO-Link:
flashing
Output indicator × 2 (orange)
Ratings
Supply voltage
SIO: 12 to 24 VDC including 10% of ripple (P-P)
IO-Link: 18 to 24 VDC including 10% of ripple (P-P)
(SELV and LIM or Class 2)*
1
Current consumption
40 mA max.*
2
Control output
Push-Pull × 2 outputs, max. 100 mA/24 VDC (total for
2 outputs)
Residual voltage: 1.8 V or less
External input
Teaching input, smart task input
Connection type
Connector type: M8, 4-pin
Circuit stabilization time
With 1 D3RF/D3WF unit inter-connected: 300 ms, with
16 D3RF/D3WF units inter-connected: 350 ms
D4RF: 300ms
CDA + CD22: 2.5 s
CDA + TD1: 350 ms
Protection circuit
Reverse connection protection, overcurrent protection
Environmental
resistance
Installation location
Indoor use
Operating temperature/
humidity
−25 to +55°C (no freezing)/35 to 85%RH (no con-
densation)
Storage temperature/humidity −40 to +70°C (no freezing)/35 to 95%RH (no con-
densation)
Vibration resistance
10 to 55 Hz; double amplitude 1.5 mm; 2 hours in each
of the X, Y, and Z directions
Shock resistance
Approx. 50 G (500 m/s
2
); 3 times in each of the X, Y,
and Z directions
Degree of protection
IP50 (According to IEC 60529, not UL certified)
Pollution degree
2 or less
Operating altitude
2000 m or less
Applicable
regulations
EMC
EMC directive (2014/30/EU)
Environment
RoHS directive (2011/65/EU), China RoHS (MIIT Order
No. 32)
Applicable standard
EN 60947-5-2
Company standards
Noise resistance: Feilen Level 3 cleared
Weight
Approx. 16 g
Material
Housing and protective cover: PC
Included accessories
Instruction manual
*1. Use a Class 2 power supply or a power supply that conforms to the SELV circuit (Safety Extra-Low
Voltage) and the LIM circuit (Limited Energy Circuit).
*2. Not including control output load current.
UL Satisfaction Ratings
* Depending on the number of fiber amplifiers and
displacement sensor amplifier units connected to
the UC2, the total load current of the control out put
and the ambient temperature are limited as follows:
When power is supplied to fiber sensor and/or displacement sensor
amplifiers in parallel
D3RF/D3WF series: up to 3 units
Input: 12-24 VDC, Max. 0.14 A Class 2
Output: 12-24 VDC, Max. 0.1 A Class 2
Maximum Ambient Temperature 55
°C
D3RF/D3WF/D4 series: up to 2 units
Input: 12-24 VDC, Max. 0.14 A Class 2
Output: 12-24 VDC, Max. 0.1 A Class 2
Maximum Ambient Temperature 55
°C
D3RF/D3WF series and CDA-M/CDA-S
:
up to 8 units
Input: 12-24 VDC, Max. 0.14 A Class 2
Output: 12-24 VDC, Max. 0.1 A Class 2
Maximum Ambient Temperature 50
°C
D3RF/D3WF/D4 series: up to 5 units
Input: 12-24 VDC, Max. 0.14 A Class 2
Output: 12-24 VDC, Max. 0.1 A Class 2
Maximum Ambient Temperature 50
°C
D3RF/D3WF series: up to 16 units
Input: 12-24 VDC, Max. 0.08 A Class 2
Output: 12-24
VDC, Max. 0.04 A Class 2
Maximum Ambient Temperature 45
°C
D3RF/D3WF/D4 series and CDA series: up to 8 units
Input: 12-24 VDC, Max. 0.14 A Class 2
Output: 12-24 VDC, Max. 0.1 A Class 2
Maximum Ambient Temperature 45
°C
D3RF/D3WF/D4 series: up to 16 units
Input: 12-24 VDC, Max. 0.08 A Class 2
Output: 12-24 VDC, Max. 0.04 A Class 2
Maximum Ambient Temperature 40
°C
When power is supplied only to a UC2-IOL unit
D3RF/D3WF/D4 series: up to 2 units
Input: 12-24 VDC, Max. 0.284 A Class 2
Output: 12-24 VDC, Max. 0.1 A Class 2
Maximum Ambient Temperature 55
°C
D3RF/D3WF series: up to 3 units
Input: 12-24 VDC, Max. 0.296 A Class 2
Output: 12-24 VDC, Max. 0.04 A Class 2
Maximum Ambient Temperature 55
°C
D3RF/D3WF/D4 series: up to 3 units
Input: 12-24 VDC, Max. 0.276 A Class 2
Output: 12-24 VDC, Max. 0.04 A Class 2
Maximum Ambient Temperature 50
°C
One D3RF/D3WF/D4 series and one CDA series
Input: 12-24 VDC, Max. 0.292 A Class 2
Output: 12-24 VDC, Max. 0.1 A Class 2
Maximum Ambient Temperature 50
°C
This device complies with part 15 of the FCC Rules.
Operation is subject to the following two conditions: (1) This device may not cause harmful interference,
and (2) this device must accept any interference received, including interference that may cause
undesired operation.
* This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant
to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against
harmful interference when the equipment is operated in a commercial environment. This equipment
generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance
with the instruction manual, may cause harmful interference to radio communications. Operation of this
equipment in a residential area is likely to cause harmful interference in which case the user will be
required to correct the interference at his own expense.
●
Support for the China RoHS directive
For details on the support for the China RoHS directive (the Administrative Mea-
sure on the Control of Pollution Caused by Electronic Information Products), see
the following websit
https://www.optex-fa.com/rohs_cn/
OPTEX FA CO., LTD.
Ramco Innovations www.ramcoi.com 800-280-6933
-----------------------e
e
mail us
:
nsales@ramcoi.com