Description of functions
32
5.4
Parameter settings
The parameters listed below can be used to adjust the Speed Controller to the respective
application. A number of the parameters listed here are only effective in certain configura-
tions or with certain settings.
5.4.1
Current limitation values
For I
2
t current limitation, it is possible to set the peak current (I
max
) and the motor continu-
ous current (I
cont
) (see chap. 5.5, p. 36). The permissible values must be observed.
Tab. 14: Motor-specific values for motor continuous current (I
cont
) and peak current (I
max
)
Parameter
Meaning
Maximum value
Unit
Peak current (I
max
)
Value for the briefly permitted maximum current
Motor-specific
mA
Motor continuous current
(I
cont
)
Value for the continuous current to which the motor is
limited
Motor-specific
mA
Motor series
Motor continuous current (I
cont
)
a)
Peak current (I
max
)
a)
Unit
2232S012BX4(S) SC
1 000
2000
mA
2232S024BX4(S) SC
500
1 000
mA
2250…BX4(S) SCC
900
1800
mA
3242G012BX4 SC
2000
4000
mA
3242G024BX4 SC
1 000
2000
mA
3242G012BX4 SCDC
b)
1900
3800
mA
3242G024BX4 SCDC
b)
1700
3400
mA
3268…BX4 SC
1600
3200
mA
3268…BX4 SCDC
1900
3800
mA
1525U009BRC
640
1280
mA
1525U012BRC
500
1 000
mA
1525U015BRC
390
780
mA
1935S006BRC
500
1 000
mA
1935S009BRC
400
800
mA
1935S012BRC
330
660
mA
3153K009BRC
2000
3500
mA
3153K012BRC
1600
3200
mA
3153K024BRC
850
1700
mA
2610/2622…006B SC
470
950
mA
2610/2622…012B SC
230
470
mA
2214S012 BXT H SC
650
1300
mA
2214S024 BXT H SC
350
700
mA
3216W012 BXT H SC
1950
3900
mA