6 Operation
6.1 Commissioning
Before starting up the Motion Controller together with a motor the following points must be
checked:
The Motion Controller has been installed according to the specifications.
The connection cables on the supply and motor end are connected according to the requirements
(risk of polarity reversal!) and are laid so that they cannot be damaged during operation. The
maximum load values must be noted and observed. (See Chapter 8 "Technical Data").
The length of the motor connection cable does not exceed 30 cm or has been laid with appropri-
ate shielding (see chapter 3.5 "Motor wiring").
Terminals and connectors are protected against ESD.
The Motion Controller's parameters are suitably configured for the connected motor.
The power supply unit is designed according to the requirements.
Power supply
Due to the PWM of the power output stage the motor current is always larger or equal to the cur-
rent that can be measured at the supply connection U
mot
. The current information (continuous / peak
output current) in the data sheets and the adjustable parameters of the I²t current limiting refer to
the motor current and not to the supply current of the Motion Controller!
CAUTION!