XL-20 Hookup and Installation Instructions
2–2
DETAIL A
8 7
1
2
3
4
ZONE
CONTROL PANEL
POWER
SMOKE DETECTOR
9.5 - 12.2VDC
LISTED
HOUSEHOLD
THERMOSTAT
ESL 104
MODEL ESL2048
EOL RELAY
RED
BLACK
BROWN
BROWN
2.2K EOL RESISTOR
UL LISTED
SMOKE
DETECTOR
MODEL
ESL445AT
UL INSTALLATIONS REQUIRE LISTED
END-OF-LINE DEVICE. USE RESISTOR
FROM EOL22 KIT. LOOK FOR LISTING
MARK ON ITEM.
WARNING:
THIS UNIT INCLUDES AN ALARM
VERIFICATION FEATURE THAT WILL
RESULT IN A DELAY OF THE SYSTEM
ALARM SIGNAL FROM THE INDICATED
CIRCUITS. THE TOTAL DELAY (CONTROL
UNIT PLUS SMOKE DETECTOR) SHALL
NOT EXCEED 60 SECONDS. NO OTHER
INITIATING DEVICES SHALL BE CON-
NECTED TO THESE CIRCUITS UNLESS
APPROVED BY THE LOCAL AUTHORITY
HAVING JURISDICTION.
CIRCUIT CONTROL UNIT SMOKE DETECTOR
(ZONE) DELAY-SEC MODEL DELAY-SEC
_______ _____ 20______ ______ __________
PRODUCT COVERED UNDER
US PATENT #4,791,658
NOTES:
1. Connect to a grounded metal water pipe (16ga. at 15 ft.).
2. Total aux. power available (including keypad power) is 500mA max.
(180mA for UL and CSFM). Used for connection of devices.
rated from 11.5 to 13.1VDC.
3. System must be tested on a weekly basis. For information, refer to
manual.
4. Do not connect the transformer to a switch-controlled receptacle.
5. Installation of equipment and wiring methods must be in accordance
with the National Electrical Code and ANSI/NFPA No. 74.
6. UL and CSFM require backup battery standby time of 24 hours minimum.
Under normal conditions this battery will last 3 years. Use only exact
replacements.
7. Maximum of 4 keypads.
8. Limited-energy cable must be used.
9. Non-replaceable fuse (F3). Return to manufacturer if blown. Do not
solder in field.
10. Maximum for UL installations: Entry Delay, 45 sec.; Exit Delay, 60 sec.
11. Programmable trigger outputs. See manual for programming information.
12. If the Pool Zone option is enabled, program zone 4 as a delay zone and
equip all doors that have access to the pool with switches for activating
alarms, as described in the "Pool Zone Connections" paragraph later in
this section.
Compatible ADEMCO 5800 Series Wireless Devices
1. 5801 4-Button Transmitter
2. 5802 Pendant Panic Transmitter
3. 5802MN Single-Button Transmitter
4. 5802CP Belt Clip Panic Transmitter
5. 5803 3-Button Transmitter
6. 5804 4-Button Transmitter
7. 5806 Photoelectric Smoke Detector
8. 5807 Photoelectric Smoke Detector
9. 5808 Photoelectric Smoke Detector
10. 5816 Miniature Transmitter
11. 5817 3-Point Transmitter
12. 5818 Recessed Magnetic Contact Transmitter
13. 5819 Wireless Shock Processor
14. 5849 Glassbreak Detector
15. 5890 Dual-Element PIR
NOTE: The XL-20 system is not compatible with the ADEMCO bi-directional devices.
Summary of Contents for XL-20
Page 9: ...XL 20 Hookup and Installation Instructions 1 2...
Page 19: ...XL 20 Hookup and Installation Instructions 4 2...
Page 23: ...XL 20 Hookup and Installation Instructions 5 4...
Page 33: ...XL 20 Hookup and Installation Instructions 8 4...
Page 63: ...XL 20 Hookup and Installation Instructions 11 4...
Page 65: ...XL 20 Hookup and Installation Instructions 12 2...
Page 71: ...XL 20 Hookup and Installation Instructions A 6...
Page 75: ...XL 20 Hookup and Installation Instructions B 4...
Page 77: ...XL 20 Hookup and Installation Instructions C 2...
Page 79: ...XL 20 Hookup and Installation Instructions D 2...
Page 81: ...XL 20 Hookup and Installation Instructions E 2...
Page 82: ...Notes...
Page 83: ...1 9 Gl N9825V1 04 98 Copyright 1998 PITTWAY CORPORATION...