SK070003_A_gb
FGP50/MEVO
TECHNICALDATAF
GP50/MEVO
OPERATINGRANGEDIAGRAMF
GP50/MEVO
Fig. 2
X=ThermalpowerY=Pressioninthecombustionchamber
ThefiringrateshasbeenobtainedbasedontestboilersinaccordancewithEN267standardsandareindicativeofmatchingtheburnertothe
boiler.Forthecorrectoperationoftheburner,combustionchamberdimensionsmustbeinaccordancewithcurrentregulation.Incaseofnon-
compliance,contactthemanufacturer.
-1
1
3
5
7
9
11
13
0
100
200
300
400
500
600
700
800
900
1000
1100
1200
1300
1400
1500
1600
1700
1800
<
kW
>
<
mbar
>
)*30(92
* Referenceconditions:Environmenttemperature20°C-Barometricpressure1013mbars-Altitude0metre(sealevel).
MODEL
FGP50/MEVO
Thermalpowerm
in.1°st./min.2°st.-max.2°st.*
[Mcal/h]
107/204-542
Thermalpowerm
in.1°st./min.2°st.-max.2°st.*
[kW]
124/237-630
LIGHT-OILflowm
in.1°st./min.2°st.-max.2°st.*
[kg/h]
10.5/20-53
Fuel:
LIGHT-OIL1.5°Eat20°C=6.2cSt=35secRedwoodN°1
Intermittedworkingoperation(min.1stopevery24hours)twostagesprogressiveormodulating
Environmentalconditionsoperation/storage:
-15...+40°C/-20...+70°C,rel.humiditymax.80%
Max.temperaturecombustionair
[°C]
60
Nominalelectricpower
[kW]
1.1
Fanmotor
[kW]
0.55
Pumpmotor
[kW]
0.37
Nominalfanmotorcurrentabsorption
[A]
1.4
Nominalpumpmotorcurrentabsorption
[A]
1.2
Nominalauxiliaryabsorption
[A]
0.6
Powersupply:
3~400V,1/N~230V-50Hz
Electricprotectiondegree:
IP44
LIGHT-OILBURNERSTWOSTAGESPROGRESSIVE
ORMODULATING