background image

FLUID COMPONENTS INTERNATIONAL LLC

                             FLT93 Flow Switch Series

This page is subject to proprietary rights statement on last page

10

   

Doc. No. 06EN003312 Rev. D

11. Determine the set point by calculating the average of the wet and dry output signals.  (i.e., If the wet signal is 0.200

volts and the dry signal is 4.000 volts, then the calculated set point would be 2.100 volts.)

12. Record this value.

Calculated Set Point = ________ volts DC

Note:

The calculated set point must be at least 0.015 volts greater than the wet signal and 0.020 volts less than the
dry signal to ensure that the alarm will reset.

13. Slide the mode switch to the CALIBRATE position.

14. Adjust the calibrate potentiometer (R24) until the voltmeter equals the calculated set point.

15. For the appropriate alarm, determine whether the status LED is on or off (red for No. 1 or green for No. 2).

16. Follow either the Detecting Dry Condition or the Detecting Wet Condition for each level application alarm.

Detecting Dry Condition (low level alarm)

If the status LED is off, turn the set point adjustment potentiometer (R26 for alarm No. 1 or R25 for alarm
No. 2) slowly clockwise just until the LED turns on.

OR

If the status LED is on, turn the set point adjustment potentiometer (R26 for alarm No. 1 or R25 for alarm No. 2)
counterclockwise until the LED turns off and then slowly clockwise just until the LED turns on.

Detecting Wet Condition (high level alarm)

If the status LED is on, turn the set point adjustment potentiometer (R26 for alarm No. 1 or R25 for alarm No. 2)
slowly counterclockwise just until the LED turns off.

OR

If the status LED is off, turn the set point adjustment potentiometer (R26 for alarm No. 1 or R25 for alarm
No. 2) clockwise until the LED turns on and then slowly counterclockwise just until the LED turns off.

17. Slide the mode switch to the RUN position.  The status LED should be on if the sensing element is dry and off if the

sensing element is wet.

18. Monitor the voltmeter display while raising or lowering the process fluid level.  When the output signal passes

through the set point, the status LED should change states and the relay contacts should change state.

19. Reestablish the normal level condition.  Both the LED and relay contacts should reset.

20. Disconnect the voltmeter from P1.

21. Replace the enclosure cover.

Note:

The relay logic default configuration is set for the relay coil to be de-energized when the level signal is
greater than the set point value.  (i.e., The relay coil will be de-energized when the sensing element is dry.)
A recommendation is to have the relay coils energized when the process condition is normal.  This will
enable the alarm to close or open the contacts in case of a power failure.

Temperature Applications

If the adjustment by observation is not accurate enough for the application, adjustment with a voltmeter can be
accomplished using manual 06EN003246. See the Operation Section of the manual for complete instructions.

Summary of Contents for FLT93 Series

Page 1: ...lement Serial Number Also Showing FlowArrow Located near the FE enclosure It is also on the enclosure tag Electronics Serial Number It is also on the transmitter s FT enclosure tag C Recommended insta...

Page 2: ...1 megohm resistor connected to ground Connect the instrument to ground Apply antistatic agents such as Static Free made by Chemtronics or equivalent to hand tools to be used on the instrument Keep hi...

Page 3: ...Remote Wiring Pictorial FLT93 Integral Wiring Diagram Maximum Distance for AWG Connection 10 ft 50 ft 100 ft 250 ft 500 ft 1000 ft 3m 15m 31m 76m 152m 305m AC Power 22 22 22 20 18 16 Relay 6A 22 16 12...

Page 4: ...OR FLT S AND J14 IS STANDARD FOR FLT93 F 0 75 WATTS 0 21 WATTS OFF OFF 0 49 WATTS 0 25 WATTS JUMPER ALARM NO 1 RELAY DE ENERGIZED WITH LOW FLOW LOW LEVEL DRY OR HIGH TEMPERATURE RELAY DE ENERGIZED WIT...

Page 5: ...h alarm can be setup for one of three applications flow level interface or temperature The following application specific adjustment procedures are generic and can be used for setting either or both a...

Page 6: ...turn the set point adjustment potentiometer clockwise until the LED turns on With the LED on slowly turn the potentiometer counterclockwise one turn past the point at which the LED just turns off The...

Page 7: ...kwise until the LED turns off With the LED off slowly turn the potentiometer clockwise one half turn past the point at which the LED just turns on The potentiometer may have up to one quarter turn of...

Page 8: ...No 2 counterclockwise until the LED turns off and then slowly clockwise just until the LED turns on 8 If this is the only flow application alarm to be setup then skip to the Continue With the Air Gas...

Page 9: ...ontinue With the Air Gas Flow Procedure 1 Slide the mode switch to the RUN position 2 Establish the normal process flow condition For low flow alarm setups the status LED should be off For high flow a...

Page 10: ...etecting Wet Condition high level alarm If the status LED is on turn the set point adjustment potentiometer R26 for alarm No 1 or R25 for alarm No 2 slowly counterclockwise just until the LED turns of...

Page 11: ...ge is out of tolerance NOT OK The serial numbers on the control board and the sensing element must match If the serial numbers are OK then contact FCI Field Service c The Voltage is between 1 and 6 vo...

Page 12: ...secrets and proprietary information which is the property of Fluid Components International LLC FCI Disclosure of this data to you is expressly conditioned upon your assent that its use is limited to...

Reviews: