background image

FLT93 Flow Switch Series

FLUID COMPONENTS INTERNATIONAL LLC

Doc. No. 06EN003312 Rev. D

11

This page is subject to proprietary rights statement on last page

Troubleshooting

LED  ON

Although the LED is on, it may appear dim.  This is usually caused by the instrument being supplied
with 115 Vac and the Input Power Jumper Configuration set to 220 Vac.

Input power and jumper configuration:
OK: 

 See item 2, Mode Switch.

NOT OK: 

 Remove the control circuit and set the jumpers correctly.  Reinstall the control circuit and

restart the system.

LED OFF

Check the Input Power Jumper Configuration setting and verify the input power.

OK:  

See item 4, Power Supply Check.

NOT OK: 

 Remove the control circuit, set the jumpers correctly and verify the input power.  Reinstall

the control circuit, restart the system and check for proper operation.  If LED is still off go to Wiring the
Instrument, page 3.

LED BLINKING

For Liquid Flow Applications: Sensor is DRY.  Make sure the pipe is full.
For Gas Flow Applications: Heater power set too high.  Set to lower value by moving heater jumper.
For Liquid level Applications: Heater power set too high.  Set to lower value by moving heater jumper.
For Liquid Interface Applications:  Set the heater power to the maximum value to achieve the maximum
signal difference between the two liquids.  For liquid applications, it is normal for the LED to blink if
the element goes dry.  Go to item 2, Mode Switch.

1. Is the Yellow LED

on,off, blinking, or
dim?

2. Mode Switch

Make sure the mode switch is in the “RUN” position.

OK:  

See item 3, Signal Voltage Observation.

7. Alarm Switch Point

Settings

Remove the Heater Wattage Control jumper.  Measure the signal voltage at P1, Terminals 1 and 2.

a) The voltage is 0 volts +/- 25 mV:

OK: 

 Reinstall the jumper and wait 5 minutes.  Go to c) or d) which ever is applicable.

b) The voltage is out of tolerance:

NOT

 

OK:  

The serial numbers on the control board and the sensing element must match.  If the

serial numbers are OK then contact FCI Field Service.

c) The Voltage is between 1 and 6 volts and changes with flow or level changes:

OK:  

 See item 7, Alarm Switch Point Settings.

d) The voltage is still about 0 volts:  or  the voltage is over + 7 volts:  or  the voltage is negative,

between -1 and -6 volts and changes with flow or level changes:
Not OK:  

Sensing element not wired correctly or defective. Incorrect wiring on remote instruments

is not uncommon upon initial installation.  For integral installations, see item 5 in this section or for
remote installations, see item 6 in this section.

Measure the voltage at P1 terminals 2 to 4.

Voltage is 0 volts: NOT OK; 

  Contact FCI Technical Service.  Replace with spare control board.

3. Signal Voltage

Observation

Turn off the power and remove the control circuit. Check sensing element connections.

Sensor Failure:

 

Call the Factory

Sensors are OK: 

 

See item 7, Alarm Switch Point Settings.

Turn off the power and remove the control circuit. Check the flow element connections versus the
wiring diagram.

Remote cable incorrectly wired or damaged:  

Repair and restart the system.

Sensor Failure:

 Call the Factory

Sensors are OK:  

See item 7, Alarm Switch Point Settings.

Make sure that the jumpers are set correctly.  The related settings are the "Alarm Duty", "Alarm
Quantity" and the "Energization".  Refer to the previous tables or the bottom side of the control circuit
for more information.

Using the Mode Switch set to Cal, check and record the alarm settings.  Compare these setting to the
signals generated by the process and make adjustments if necessary.

5. Sensor Element

Check for
Integral Installation

6. Sensor Element

Check for Remote
Installation

If you continue to experience problems with the instrument, see the Troubleshooting Section in the FLT93 Manual, document
number 06EN003246. To acquire a manual, call your local FCI Sales Representative.

4. Power Supply

Check

Summary of Contents for FLT93 Series

Page 1: ...lement Serial Number Also Showing FlowArrow Located near the FE enclosure It is also on the enclosure tag Electronics Serial Number It is also on the transmitter s FT enclosure tag C Recommended insta...

Page 2: ...1 megohm resistor connected to ground Connect the instrument to ground Apply antistatic agents such as Static Free made by Chemtronics or equivalent to hand tools to be used on the instrument Keep hi...

Page 3: ...Remote Wiring Pictorial FLT93 Integral Wiring Diagram Maximum Distance for AWG Connection 10 ft 50 ft 100 ft 250 ft 500 ft 1000 ft 3m 15m 31m 76m 152m 305m AC Power 22 22 22 20 18 16 Relay 6A 22 16 12...

Page 4: ...OR FLT S AND J14 IS STANDARD FOR FLT93 F 0 75 WATTS 0 21 WATTS OFF OFF 0 49 WATTS 0 25 WATTS JUMPER ALARM NO 1 RELAY DE ENERGIZED WITH LOW FLOW LOW LEVEL DRY OR HIGH TEMPERATURE RELAY DE ENERGIZED WIT...

Page 5: ...h alarm can be setup for one of three applications flow level interface or temperature The following application specific adjustment procedures are generic and can be used for setting either or both a...

Page 6: ...turn the set point adjustment potentiometer clockwise until the LED turns on With the LED on slowly turn the potentiometer counterclockwise one turn past the point at which the LED just turns off The...

Page 7: ...kwise until the LED turns off With the LED off slowly turn the potentiometer clockwise one half turn past the point at which the LED just turns on The potentiometer may have up to one quarter turn of...

Page 8: ...No 2 counterclockwise until the LED turns off and then slowly clockwise just until the LED turns on 8 If this is the only flow application alarm to be setup then skip to the Continue With the Air Gas...

Page 9: ...ontinue With the Air Gas Flow Procedure 1 Slide the mode switch to the RUN position 2 Establish the normal process flow condition For low flow alarm setups the status LED should be off For high flow a...

Page 10: ...etecting Wet Condition high level alarm If the status LED is on turn the set point adjustment potentiometer R26 for alarm No 1 or R25 for alarm No 2 slowly counterclockwise just until the LED turns of...

Page 11: ...ge is out of tolerance NOT OK The serial numbers on the control board and the sensing element must match If the serial numbers are OK then contact FCI Field Service c The Voltage is between 1 and 6 vo...

Page 12: ...secrets and proprietary information which is the property of Fluid Components International LLC FCI Disclosure of this data to you is expressly conditioned upon your assent that its use is limited to...

Reviews: